FA104085
24/01/2018
Issue: Can you get a run status indication from my ATV28 drive?
Product Line: ATV28
Environment: All
Cause: N/A
Resolution: Yes. You can go to the I/O - menu and if want to have logic input to be high when above 0hz which is a valid reference when have direction signal may want to set R2 to Frequency threshold attained ( FtA ).
When set logic output to this it is in a state of 1 (on or closed) if the motor frequency is greater than or equal to the frequency threshold set by the Ftd parameter in the SEt - menu
(You can set FTD to a value of 1 and therefore it will not indicate running unless have frequency greater than 0hz.)