FA104493
24/01/2018
Issue: Does the ATV28 unit have skip frequencies that can be set into the unit?
Product Line: ATV28
Environment: All
Cause: N/A
Resolution: This drive has one skip frequency that can be set in menu SEt. The code for the parameter is JPF and operates at a range of 2hz around JPF setting.