Win a $4,000 Switchboard Upgrade
Learn How

Can the ATV31...A model be setup to use the integral speed pot dial for reference adjustment, but use the LI logic input for a run forward command?

FA112217

14/07/2020

Issue:   
Set up Start/Stop from terminals and Speed Reference from Dial on ATV31...A.
 
Product Line:   
ATV31
 
Environment:  
ATV31**A models
 
Cause:  
N/A
 
Resolution:   
Yes.  In the IO menu, set parameter tCC to 2C.  This assigns LI1 as run forward command.  In the CtL menu, set parameter Fr1 to AIP.