What is the typical control circuit consumption at 24VDC for the U-Line LUB32?

FA112767

4/03/2020

Issue:
LUB32 consumption

Product Line:
Tesys U Motor Starters and Protectors

Environment:
n/a

Resolution:
The consumption depends on which control unit is installed into the Base unit. 
For a standard control unit inrush is 220mA and the sealed is 70mA.
For an advanced control unit inrush is 220mA and the sealed is 70mA.
For a multifunction control unit inrush is 200mA and the sealed is 75mA.