FA114207
8/07/2020
Issue:
Can the 0-10VDC analog input be configured for 0-5VDC?
Product Line:
Altivar 71
Environment:
All
Cause:
DC scaling
Resolution:
Yes, There are scaling parameters for AI1 in menu 1.5 that allow you to change the min and max values of the speed reference (UIL1 and UIH1 for AI1). Once these parameters are set, the speed referrrence is linearly scaled between them.