What is the power terminal lug data for the LC1D09, LC1DT20, LC1D12, and LC1DT25 contactor?

FA109066

28 September 2021

Issue:
Power terminal lug data required for the 9 and 12 amp rated Tesys D contactors

Product Line:
IEC Contactors and Starters

Environment:
Tesys D Contactors

Resolution:
For contactors with screw clamp terminals:
stranded cable w/o cable end : One or Two #18-10 AWG per terminal.
stranded cable w/cable end: One or Two #18-10 AWG per terminal.
solid cable: One or Two #18-8 AWG per terminal.
;