Issue:Jog function requirements on ATV61/71
Product Line:Altivar 61/71
Environment:All models and serial numbers
Cause:The Jog will not start when the assigned logic input goes high.
Resolution:The Jog and Preset speed functions both depend on a run command being active, typically LI1 to be enabled if in 2 wire control mode.