Frequently asked questions
ATV61: Why can the Forced Local parameter not be change from NO?
FA285498
28 July 2022
Issue:Cannot change Forced Local parameter from NO
Product line:
ATV61, ATV71, Altivar 61, Altivar 71
Environment:
All
Cause:
Customer wants to use Forced Local but the drive will not allow the change.
Resolution:
Forced local is not compatible with the Profile set to IO. To use the Forced Local function, the Profile needs to be set to Separate or Not Separate.