2000M

SURROUND 2000 SER METAL

Catalogue Number: 2000M

Discontinued

2000M
Colour: Brushed Aluminium
Colour: Per UOM Std.
  • Brushed Aluminium 1 PCE 1
  • Chrome 1 PCE 1

Specifications

hide show
Range of product
  • Gangbusters
  • Series 2000
    • Product brand
      Clipsal
      Mounting position
      horizontal
      Device mounting
      flush
      Type of installation
      indoor
      Surface treatment
      metallic
      Depth
      12 mm
      Length
      116 mm
      Width
      76 mm

      Documents & downloads

      hide show
      Filter items
      • All

      • CAD Files and Packs

      • Installation Instruction

      • Product Environmental

      • Operating Manuals

      • Specifications

      • Certificates (MSDS)

      Frequently Asked Questions

      hide show

      Do you have a 2000MF round mounting block with a diameter of 800?

      Yes the part number is 2000MF800.

      Is it Possible to Upgrade a 1600A NW16 Breaker to a 2000A NW20 by Changing the Sensor Plug.

      No. It is not possible. As per the attached document the NW16 have sensor rating only from 800 - 1600A, So a 2000A Sensor Plug is not suitable for NW16 Breaker. So it can not be changed. 

      What is the altitude derating for a TeSys D-Line contactor?

      Issue:​
      What is the altitude derating for a TeSys D-Line contactor?

      Product Line:
      Digest 177 Section 18 : Contactors and Starters, IEC

      Environment:
      North American Products

      Resolution:
      The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

      Voltage
      3500m x 0.90
      4000m x 0.80
      4500m x 0.70
      5000m x 0.60

      Current
      3500m x 0.92
      4000m x 0.90
      4500m x 0.88
      5000m x 0.86

      For example, an LC1D80 at 5000 meters:
      - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
      - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



       

      What is part number for 200mm pull cord wall fan?

      The part number for 200mm pull cord wall fan is 7108A.

      What is part number for 200mm window fan?

      No unfortunately there is no 200mm window fan available.

      What is the part number for standard din rail?

      The part number for standard din rail is NSYSDR200B. It is 7.5mm deep by 2000mm long.

      What is the effect of altitude on ATV312?

      Product Line:
      All ATV312 and ATV31

      Environment:
      High altitude, more than 1000m

      Cause:
      What is the effect of the high altitude on the drive.

      Resolution:
      For all ATV312, less than 1000m, no derating.
      For single-phase supplie and corner grounded distribution networks, up to 2000m, derateing 1% per 100m.
      For three-phase supplies, up to 3000m, derating 1% per 100m.




       

      Is it possible to mount a weathershield power point on a pole ?

      Weather shield enclosure will line up with the 2000MF range, screw mountings will go on an angle to the pole, opposing the enclosure and may be tricky.
      Available standard as white. If diameter surface is less than 300mm you may be able to use a 56PMK.
      2000MFV range has a large amount of variable for different sized diameter surfaces.
      Please see following link for complete range of sizes
      https://www.clipsal.com/Trade/search-results?q=2000mf
       

      What is the maximum altitude an ATV61 or ATV71 series drive can be used at?

      Issue:
      What is the maximum altitude an ATV61 or ATV71 series drive can be used at?

      Product Line:
      Altivar 61, Altivar 71 series drives.

      Environment:
      All models, All serial numbers.

      Cause:
      Elevation vs current rating

      Resolution:
      The Altivar  61 and 71 series drives can be used at full rating up to 1000 meters above sea level. They must then be derated by 1% for every additional 100 meters up to a maximum of 3000 meters above sea level.
      Note that the ATV61H***S6X and ATV71H***S6X drives must not be used with corner grounded systems at altitudes above 2000m.

      Do you have a 45RU data cabinet 800mm Wide X 1000mm Deep?

      Yes, the part number is 3106N45C810-BK.

      What is the part number for a wall ex-fan 200mm with cut out of 230mm?

      The part number for a wall ex-fan 200mm with cut out of 230mm is - 7105A

      For further information , visit link below:-

      https://www.clipsal.com/Trade/search-results?q=7105A
      User-added image
       

      What is the cut out size for 7105A, 200mm window exhaust fan?

      The cut out size for 7105A, 200mm window exhaust fan is 230mm diameter. 7105A is remotely switched with auto shutters,38W, IPX4, 600m³/hr.
      For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=7105A
      User-added image

      What is the part number for an LED flood light that has 20000 Lumens output?

      The part number for an LED flood light that has 20000 Lumens output is - FLH200LED

      For further information , visit link below:-
      User-added image
      https://www.clipsal.com/Trade/search-results?q=FLH200LED
       

      What is the diameter of a 94CL ceiling light

      The diameter is 200mm x 95mm

      What are the dimensions for SIGN/BPA & SIGN/CPA?

      90mm (H) x 200mm (W)

      Is there a 200mm exhaust fan available?

      Yes, the part number is 7106A

      How do I get Modsoft to open up to full screen display while I try to run it under WIN 2000?

      The command to get Modsoft to change window size is ALT+<ENTER>; however Modsoft is not supported under WIN 2000. Users may try running the application under it; however successful operation cannot be guaranteed. One of the common problems is Modsoft will not open up to full screen. Regrettably there is no means to resolve this issue other than to reinstall the software under a supported OS, such as WIN 95, WIN 98 or DOS.


      Legacy KB System (APS) Data: RESL171500 V1.0, Originally authored by on , Last Edited by on
      Related ranges: Modsoft

      What is the part number for a 200mm wall ex-fan with auto shutters?

      The part number for a 200mm wall ex-fan with auto shutters is - 7106A
      For further information , visit link below:-
      https://www.clipsal.com/Trade/search-results?q=7106A
      User-added image

      What is part number for 200mm Tal plus duct?

      The part number for 200mm Tal plus duct is a PL500200D.

      for more information on this part please refer to https://www.clipsal.com/Trade/search-results?q=PL50200D

      What is the part number for skirting duct 50mm deep and 200mm high ?

      the part number for skirting duct 50mm deep and 200mm high is - PL50200D

      For further information , visit link below:-
      https://www.clipsal.com/Trade/search-results?q=PL50200D
       

      Can you get a double power point with 2 USB ports?

      No, unfortunately this part is unabaliable. However, there is a single power point with 2 USB ports avaliable. This is avaliable in two diffrent styles, 2000 Series or the Classic 2000 Series. The part numbers are (Classic 2000) C2015USB2C and (2000 Series) 2015USB2C.
      Some of there key features are:
      • Twin 30USBCM USB Chargers
      • Surge, over-current and over-temperature protection
      • Cable compensation for optimised charging
      • Meets BC1.2 USB Charging Standard
      • Meets Class V Energy Efficiency in standby
      • Certified to all relevant safety and EMC requirements for Australia

      For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=2015USB2C
                                                    Or https://www.clipsal.com/Trade/Products/ProductDetail?catno=C2015USB2C

       
       
       

       

      Can you get a plate larger than 6 gang in the 2000 series?

      Not directly, but using the 2000/2 or 2000h2 series you can fit 2 plates under one surround.

      What is the part number for a 45RU data cabinet , 800mm wide and 1000mm deep?

      The part number for a 45Ru data cabinet that has dimensions of W800m x D1000mm is - 3106N45C810

      For further information , visit link below:-
      https://www.clipsal.com/Trade/search-results?q=3106N45C810

      Starting Register number in Modbus Read functions

      Goals and Symptoms

      When performing Modbus read commands, it is important to apply the right starting register address in the read function. Otherwise, the wrong register will be accessed from the meter, giving unexpected data for the meter parameter being read.


      • Meter is functioning as expected. The front panel values for voltages and currents are within expected ranges for the system being monitored. However, modbus read functions from a master station (e.g. a PLC) give values that do not correspond to the front panel values.

      Facts and Changes

      Modbus, modbus rtu, function read, modbus map, holding register, staring register, function 03, modbus read packet

      Causes and Fixes

      Cause
      One probable cause would be that, the modbus function read command is not pointing to the right registers. The modbus protocol requires an offset to be introduced in the starting register address when reading the slaves register.

      Resolution

      When reading the meter parameters, the Master must send the device a Read Holding Registers packet. This packet must specify a start register and the number of registers to read. When the function read is received, the slave responds with a packet containing the registers in the range defined in the read request.

      However, consider the 3710 Modbus map, which states that according to the MODBUS protocol, in response to a request for address 4xxxx, the master reads register xxxx-1 from the slave (3710). For example, a request for register 40011 returns register 10 from the slave.

      What does the above statement mean? Why is an offset required?

      Holding registers, by default, are defined the 4xxxx range, the first holding register staring at 40001. The starting register in the read packet is, on the other hand, numbered from zero. Hence, the start register zero automatically points to holding register 40001, starting register one points to holding register 40002, etc. The fact that the first holding register is 40001 and not 40000 explains the offset that needs to be introduced in the starting register number.

      Hence, considering the 3710 Modbus Map statement, if the Master needs to read register 40011, then the corresponding starting register that needs to be put in the read function would be 10 (0A hex) since register 40011 is the register 10 from the first holding register, 40001:
      40001 > Start register 0
      40002 > Start register 1
      40003 > Start register 2
      40004 > Start register 3
      40005 > Start register 4
      40006 > Start register 5
      40007 > Start register 6
      40008 > Start register 7
      40009 > Start register 8
      40010 > Start register 9
      40011 > Start register 10

      The Modbus Read Request Packet for a master reading 3 registers from a slave with unit ID 100 (64 Hex) and for starting register of 40011 should be:
       

      Slave ID
      Function
      Start Register (40011)
      # of Registers
      CRC Checksum
      64
      03
      00
      0A
      00032C3C


      To summarize, when looking at a modbus map, the starting register number to be used in the read function:

      Start Register = Modbus Register 40001.

       

      Original article#12774

      Public

      All content © 1992-2007 Schneider Electric


      Legacy KB System (APS) Data: RESL188799 V1.0, Originally authored by KBAdPM on 11/03/2007, Last Edited by KBAdPM on 11/03/2007
      Related ranges: Modbus / JBus

      Sepam EcoFit offer

      Schneider Electric offers a retrofit solution for converting Sepam 2000's to the new Sepam 1000+ relays.
      ECOFIT S2000 Leaflet - SERED111087EN.pdfECOFIT S2000 Leaflet - SERED111087EN.pdfECOFIT SEPAM 2000 Customer Presentation Rev1a.pptECOFIT SEPAM 2000 Customer Presentation Rev1a.ppt

      I am looking for a wall fan with a 240mm cutout and is physically approx 300mm square

      You can use a Clipsal 7106A or 7108A both have a 230mm cut out and are 271mm square

      Is Event Notification Solution 6.4 /Active Pager Module 6.4 (ENS 6.4, APM 6.4) compatible with SQL 2000?

      ENS 6.4 is only supported with SQL 2005 and SQL 2008 instances.
      During the install, SQL 2000 instances can be chosen, but the install will not complete if a SQL 2000 instance is selected.


      Legacy KB System (APS) Data: RESL206608 V1.0, Originally authored by MaTh on 11/09/2011, Last Edited by MaTh on 11/09/2011
      Related ranges: Paging Module, SMS Add-on

      What is the Pin out detail for the Modbus programming cable 110 XCA 20 3000?

      The pin out details of the Modbus programming cable 110 XCA 20300 is as shown in the attached.

       

      Can I fit a duct onto a 6600A 3 in 1?

      Yes, the 6600A can have a 200mm duct fitted.

      What would be the part number for a grill to suit a 200 mm exhaust fan.

      The part number would be CEOL200.
      This is an Outlet louvre to suit 200mm diameter ducting.
      For more information on this product please visit the Clipsal.com website on the link provided https://www.clipsal.com/Trade/search-results?q=ceol200

       

      What is the part number for a 200mm window exhaust fan?

      The part number for a 200mm window exhaust fan is - 7105A

      For further information , visit link below:-
      https://www.clipsal.com/Trade/search-results?q=7105A
      User-added image

      How many copper FIPIO or FIPWAY network segments can be joined into one copper FIP network and what is the total length possible?

      Up to 5 copper FIPIO or FIPWAY network segments can be joined using either TSXFPACC6 (electrical) or TSXFPACC8 (optical) repeaters to get a total length of 5000m of copper cabling. Each individual segment is limited to 1000 meters in length. This figure includes all trunk cabling and all drop cabling.

      Is cut out for Modena/Strato same as C2000?

      Yes, same dimensions as C2000 series.

      What is the cut out for the 7500ATP?

      290mm X 290mm with a minimum ceiling cavity of 230mm

      What version of SQL Server is used with the different versions of ION Enterprise?

      ION Enterprise 3.0 MSDE 1.0 (SQL Server 7.0)
      ION Enterprise 4.0 MSDE 1.0 (SQL Server 7.0)

      ION Enterprise 4.5 MSDE 1.0 (SQL Server 7.0)

      ION Enterprise 5.0 MSDE 2000 (SQL Server 2000)

      ION Enterprise 5.5 MSDE 2000 (SQL Server 2000)

      NOTE: It is possible to use ION Enterprise 5.5 Service Pack 2 with SQL Server 2005, but some modifications are required. See KB articles 12704, 12708 and 12823 for detailed information.

      ION Enterprise 5.6 SQL 2005 Express (SQL Server 2005)
      NOTE: ION Enterprise 5.6 will use an existing MSDE 2000 instance, but will install SQL Express on new systems if there is no pre-existing SQL Server instance.
      ION Enterprise 6.0 SQL 2005 Express with Reporting Services SP3 (SQL Server 2005 SP3 with Reporting Services)
      NOTES: The ION Enterprise 6.0 installer will upgrade an existing MSDE 2000 instance to SQL Server 2005 Express with Reporting Services. ION Enterprise 6.0 does not support SQL Server 2000. It also does not support SQL Server 2008

      • Original article#16492

        Public

        All content © 1992-2009 Schneider Electric


      Legacy KB System (APS) Data: RESL188782 V3.0, Originally authored by KBAdPM on 11/02/2007, Last Edited by JaMc on 10/15/2009
      Related ranges: ION Enterprise V5.5, ION Enterprise V5.0, ION Enterprise V4.5, ION Enterprise V4.0

      Is ION Enterprise 5.6 compatible with Microsoft Office XP or 2000?

      Microsoft (MS) Office XP or 2000 are older versions of the MS Office suite. The Commissioning Guide for ION Enterprise recommends Excel 2003 as a minimum version and the earlier versions have not been tested by the Software department, however, there are customers who have successfully installed MS Office 2000 and ION Enterprise 5.6 together. If there are any problems using an older version of Office, the resolution is to upgrade to Office 2003.

      Last Revised: November 22, 2007
      Applies To: ION Enterprise 5.6
      Public
      All content © 1992-2007 Schneider Electric


      Legacy KB System (APS) Data: RESL189470 V1.0, Originally authored by KBAdPM on 11/23/2007, Last Edited by KBAdPM on 11/23/2007
      Related ranges: ION Enterprise V5.6

      How can I find a lost code on Sepam 2000?

      To find the lost code on a Sepam 2000 prior to 96/49:

      go to the control logic in which the code (password) is given
       
      To find the lost code of a Sepam 2000 later than or equal to 96/49, there are 2 options:

      If the code has not been modified using the Pocket PC:
      • go to the control logic in which the code (password) is given.
      If the code has been modified using the Pocket PC: 
      • re-load the control logic using LOGIPAM making a note of the code (password) used.

      Note: The standard code (password) for the control logics is 6543210.

      What is the dimensions and IP Rating for the PDL 94FL ?

      Dimensions 200mm Diameter    95mm Depth

      IP rating IP44 weather protected, UV stabilised and double insulated.  Application Indoor / Outdoor.

      What are the dimensions for 10800A

      The dimensions for 10800A are 200mm (H) x 123mm (W) x 112mm (D)

      What is the cut out for the C2016/2?

      The cut out for the C2016/2 is 30mm (H) X 200mm (W).

      AP7003 (Network Air 1000) mobile air conditioner manual, install and parts

      Issue:
      AP7003 (Network Air 1000) Install Manual 

      Product line: 
      AP7003 (Network Air 1000)

      Environment: 
      All Serial Numbers 

      Cause: 
      Operations Manual 

      Resolution:  
      See attached document

       

       

       

      What is the dimensions of the 534P16S multi plate

      Dimensions 220mm x 220mm square

      Configuring Native USB Power Options in Windows 2000, XP, or 2003

      Issue:
      How to configure native USB power option.

      Product Line/s:
      Back-UPS
      Smart-UPS

      Environment:
      Microsoft Windows 2000, XP or 2003

      Cause:
      Installation / Set-up

      Solution:

      Please see attached PDF.

      Will the 2000pp fit the C2000 series?

      No, unfortunately you will need to use a C2000PP paint protector.

      For further information please visit www.clipsal.com/Trade/Products/ProductDetail?catno=C2000PP

      What is the separator for a 15092

       The separator part code is 27001

      what is the height of the 6600a / minimum clearance required ?

       
       
       
       
      The 6600a is 200mm high and minimum clearance required  is a  500mm high cavity allowing 300mm minimum above the fan.
      For more information on this product please visit the Clipsal web site on the link provided
      https://www.clipsal.com/Trade/search-results?q=6600a

      What is the max and min enclosure depth for the INS320 with extended rotary handle

      The min depth = 204mm and the max depth = 600mm

      Can you get a cooker switch such as the C2031/45 in slimline SC series?

      No, cooker switches are only available in C2000, 2000 and Saturn series.

      Error Restoring SQL2000 database backup on SQL Server 2012

      Issue:
      The database was backed up on a server running version 8.00.0760. That version is incompatible with this server, which is running version 11.00.3128.

      Product  Line:
      SQL Server 2000
      SQL Server 2012

      Environment:
      SQL Server Database Restoration

      Cause:
      It is not possible to restore a SQL Server 2000 database on SQL Server 2012.

      Resolution:
      You will need to restore the database on an instance of SQL Server 2005, 2008 or 2008 R2 first, then back it up from there, then restore the new backup on SQL Server 2012.



      Which type of switch mechanism is used for the wall switch on the SILC system?

      A standard bell press mechanism is used (momentary action). The products are currently in our Electrical Accessories range and the references are: 30PBBP-WE (suits Standard ranges, 2000, C2000, etc) and 60PBBP (suits Saturn and Saturn ZEN).
      Please follow link below to find out more information of this product:
      https://www.clipsal.com/Trade/search-results?q=silc