Batten Holders

White Electric | Batten Holders

Batten Holders

Item Number: 2530-WE

Datasheet

Specifications

Design

Product brand

Clipsal

Product or component type

BC lamp holder adaptor

Colour tint

white electric

Physical

Provided equipment

  • lamp holder
  • skirt
    • Device mounting

      surface

      [Ue] rated operational voltage

      250 V

      Connections - terminals

      4 terminals

      EU RoHS Directive

      Pro-active compliance (Product out of EU RoHS legal scope)

      Environmental Disclosure

      ENVPEP120506EN

      Others

      Package 1 Weight

      72 g

      Package 1 Height

      70 mm

      Package 1 width

      70 mm

      Package 1 Length

      65 mm
      Show all specifications

      Documents & downloads

      hide show
      Filter items
      • All

      • Product Brochures

      Frequently Asked Questions

      hide show

      Where can I find a copy of the Installation Guide for the ATS48 Soft Starters?

      Issue:
      Installation Guide request for the ATS48 Soft Starters

      Product Line:
      Altistart 48

      Environment:
      All

      Cause:
      Needs to find a copy of the ATS48 installation Manual

      Resolution:
      The manual number is S1A37491
      This is the Altistart 48 Y-Range Soft Start Controllers Instruction Bulletin.  Click on the link below or see the attachment to download a copy of the manual.

      https://www.schneider-electric.com/resources/sites/SCHNEIDER_ELECTRIC/content/live/FAQS/253000/FA253372/en_US/S1A37491.pdf

      Why is the LCD display screen blank on a Micrologic Power or Harmonic type trip unit on a Powerpact P frame, R frame, or Masterpact circuit breaker?

      Issue:
      Why is the display blank on the trip unit?

      Product Line:
      Powerpact P frame, Powerpact R Frame, Masterpact NT, Masterpact NW

      Environment:
      Applied to Powerpact and Masterpact breakers with trip units with LCD displays.

      Cause:
      Need to power display of the trip unit without external power supply.

      Resolution:
      The LCD display on a Micrologic P or H trip unit will be blank unless the trip unit is energized.  Energization requires one of the following sets of conditions:
      1. The trip unit is energized by an external 24 Vdc applied to terminals F1-F2 (F1 negative-F2 positive)
      2. The trip unit is energized by an FFTK or HHTK test kit
      3. There is at least 100 V between two phases, AND the load reaches approximately 20% of the breaker's rated current.
      • Note that the display will not power up with primary injection testing unless one of the conditions in bullet 1 above is met.
      • Note that Ammeter trip units do not require external power and the display will come on with sufficient current flow alone.
      See the following bulletins for more information on these trip units.
       

      Why does the load side of the shorting contactor connect to A2, B2 and C2 on the ATS48 soft start?

      Issue:
      Shorting contactor wiring

       Product Line:
       ATS48

      Environment:
      All models and serial numbers
       
      Cause:
      None
       
      Resolution:
      The A2, B2 and C2 terminals on the soft start provide a current path through internal current transformers.  This provides overload protection when the shorting contactor is enabled.
      Refer to page 81 in the ATS48 Installation Guide for a wiring diagram. 

      What is a good source of information for the ATS48 soft start?

      Issue:
      Information is needed to facilitate installation and programming

      Product line:
      Altistart ATS48

      Environment:
      All models, all serial numbers

      Cause:
      None

      Resolution:
      Instruction Bulletin, S1A37491, includes information for installing and programming the ATS48.
      Instruction Bulletin, 30072-451-28, is a Maintenance and Repair manual.

      Use this URL to get to the ATS48 product page:
      https://www.schneider-electric.com/en/product-range/689-altistart-48/

      Is there a fixed angle batten holder available?

      Yes, the fixed angle Batten Holder is a  531. There is also an angled adaptor to suit 530 and 2530 series batten holders which is a 530AWP.

      Some of the key features are:
      • 250W
      • With built-in fastening Ppugs and screws
      • Easily removable cover by 120 deg rotation and visual indicators
      • Front access to terminal slots allowing easy adjustment of terminals, even after installation
      For further information please visit https://www.clipsal.com/Trade/search-results?q=batten%20holders&p=1
       

      What is the Clipsal lamp holders rated to for a heat lamp

      Most have a rating between 150-200, the 2530 in white has a 250W rating.
      Note this is a Bayonet Cap BC fitting not an Edison screw lamp holder 