coupling pvc plain/scr 16mm

COUPLING PVC PLAIN/SCR 16MM

Catalogue Number: 258/16
coupling pvc plain/scr 16mm
Colour: Grey
Colour: Per UOM Std.
  • Grey 1 PCE 1

Specifications

hide show
Product brand
Clipsal
Material
PVC (polyvinyl chloride)
Connector type
thread connector
Product destination
diameter: 16-16 mm tube
Standards
AS/NZS 2053
REACh Regulation
Free of Substances of Very High Concern above the threshold
REACh free of SVHC
Yes
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
Toxic heavy metal free
Yes
Mercury free
Yes
RoHS exemption information
Yes
China RoHS Regulation
 Pro-active China RoHS declaration (out of China RoHS legal scope)

Frequently Asked Questions

hide show

What is the replacement for the 25831?

The replacement for the 25831 3p 16A C curve 6kA MCB is part number A9F44316

 

How many 261/16 Clipsal saddles are there in a carton?

There are 50 16mm saddles in a carton.

Note: This information can be found in your Clipsal pocketbook right next to the part code.

Is a C60N 25801 ok to operate on 24V DC

Yes it is

Are the Clipsal Conduit Clips available in Electric Orange?

No, they are only available in grey.

This applies to the 280/16 (16mm), 280/20 (20mm), 280/25 (25mm), 280/32 (32mm), 280/40 (40mm) and 280/50 (50mm).

What is the part code for a RCBO 4P 32Amp C-curve

 Combine a mccb 25016 32Amp C-curve with a 23382 rccb = RCBO

What is the part code for a 2P 16A 6kA C-curve circuit breaker

 The part code is 25817

Does the Ritika Circuit breaker 25815 have the same dimensions as the 25823

 It has the same physical size

What would the breaking capacity be on a 25801 C60N 6A 1p breaker if used with 24V dc

The breaking capacity is 15kA

What is a 2pole, 6A, C Curve, 6kA circuit breaker

 Part code 25815 Multi 9 - Acti 9 A9F44206

Where are I/O modules installed on a PM8000 meter

Issue:
User wants to know where to install I/O modules on a PM8000 meter.
 
Product Line:
PM8000 meters
METSEPM89M2600 (Digital I/O module)
METSEPM89M0024 (Analog I/O module)

Environment:
I/O modules installation

Resolution:
*Warning:  Installation and maintenance of this device should only be performed by qualified, competent personnel that have appropriate training and experience with high voltage and current devices. Failure to follow the instructions / warnings in the Meter Installation Guide can result in permanent damage to the meter, severe injury or death.

There are 2 methods to install I/O modules on a PM8000 meter. The method to choose will depend on your PM8000 model number

If meter is PM8240 (Panel mount meter with integrated display)
I/O module to be installed on the back of the meter. 
1) remove connector's cover on back of the meter
2) Make sure that connectors on meter and I/O module align with each other. Attach I/O module to the back of the meter.
3) secure the I/O module in its location by a 5mm (5/16 in) screw
4) reattach connector's cover that was removed in step 1 to the back of I/O module
See illustration below:


If meter is either PM8243 or PM8244 (DIN rail mount meter)
I/O module to be installed on the side of the meter:
1) remove connector's cover from side of the meter
2) Hang the I/O module on your DIN rail
3) Secure I/O module to the DIN rail using Mounting clip.
4) Move I/O module using the DIN rail and attach it to the PM8000 meter> You should hear a click.
5) Secure the I/O module to the meter using a 5mm (5/16 in) screw.
6) reattach connector's cover that was removed in step 1 to the back of I/O module
See illustration below: