coupling pvc plain/scr 40mm

COUPLING PVC PLAIN/SCR 40MM

Catalogue Number: 258/40
coupling pvc plain/scr 40mm
Colour: Grey
Colour: Per UOM Std.
  • Grey 1 PCE 1

Specifications

hide show
Product brand
Clipsal
Material
PVC (polyvinyl chloride)
Connector type
thread connector
Product destination
diameter: 40-40 mm tube
Length
46-46 mm
Standards
AS/NZS 2053
REACh Regulation
Free of Substances of Very High Concern above the threshold
REACh free of SVHC
Yes
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
Toxic heavy metal free
Yes
Mercury free
Yes
RoHS exemption information
Yes
China RoHS Regulation
 Pro-active China RoHS declaration (out of China RoHS legal scope)

Frequently Asked Questions

hide show

What are the part numbers of slip type expansion couplings?

Slip Type Expansion Couplings are available from 16mm through to 50mm.The part numbers of slip type expansion coupling are as follows:
16mm = 251/16
20mm = 251/20 *
25mm = 251/25 *
32mm = 251/32
40mm = 251/40 *
* = only available in Grey
Where long conduit runs are likely to be exposed to wide variations in temperature, it is recommended that expansion couplings be used at each join. It is not recommended that Slip Type Expansion Couplings be used where the conduit run is exposed to the weather. Standard colour is Grey (GY).
Dimension details are attached.
 

What would be a longer screw to suit Clipsals round j-boxes (Junction Boxes)?

The part number would be 248/20 which is a combination screw head 20MM 3/16 BSW.

Can I get the 251/50 in orange?

No. Unfortunately, the 251/50 is the only one that comes in grey.

For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=251/50



 

Are the Clipsal Conduit Clips available in Electric Orange?

No, they are only available in grey.

This applies to the 280/16 (16mm), 280/20 (20mm), 280/25 (25mm), 280/32 (32mm), 280/40 (40mm) and 280/50 (50mm).

What is the replacement for 25834 MCB?

The replacement for 25834 MCB is A9F4432
A9F44332
A9F44332
Acti9 iC60N 3P 32A C Miniature Circuit breaker

For further information see: https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9F44332

What is the replacement for 25804 MCB?

The replacement is A9F44120.

User-added image
A9F44120
Acti9 iC60N 1P 20A C Miniature Circuit breaker

For further information see:https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9F44120

What is the part number for the bitsa box?

The part number for the bitsa box is 357TB.
Some of the key features are:
  • Tool boxes
  • 12 compartment transparent box with assorted screws, screws and quantities included
  • Includes: 357WF30 (100), 357/20 (150), 357WH12 (350), 357P30 (200), 357P20 (300), 357WH25 (100), 357PH50 (50), 357/63 (50), 357WHP32 (100), 357PH45 (100), 357/35 (100), 357/40 (100)
For further information please visit www.clipsal.com/Trade/Products/ProductDetail?catno=357TB


 

Typical 3-line drawings for Sepam Series 20, 40 and 80 current and voltage input connections

Goals and Symptoms

Typical 3-line drawings of Sepam 20/40 Feeder, Sepam 20/40 Main and Sepam 80 Main/Feeder.

Causes and Fixes

See attachment
Sepam.zip



AEDL3
Legacy KB System (APS) Data: RESL203669 V1.0, Originally authored by MiZe on 10/09/2010, Last Edited by MiZe on 10/09/2010
Related ranges: Sepam series 80, Sepam series 40, Sepam series 20

What is the replacement for 25834 and 26665?

Enclosed Altivar VFD will not run when the run command is given.

Issue:
 The enclosed VFD will not run when run command is given?

Product line:  
Enclosed ATV61 ATV71 ATV58 ATV312 

Environment:  
0 -100 horsepower 460 volts, 0-50 horsepower 208/240 volts   

Cause:
The VFD will not run when given a run command is activated?

Resolution:
Troubleshooting Enclosed VFD with HOA, Test/Normal and AFC/OFF/BYPASS switch. Terminal 24 is the neutral for the 120 V supply.
 
 
              1).   Is the RCR relay energized with the HOA switch in the Hand position? NO
a). Voltage should be present on Terminal 6 (Verify there is a jumper between 6A and 6, or does the EFLEX have a start stop push button, press the start button)
b). Verify voltage on terminal 6A (Verify HOA is in HAND position and voltage is present on both sides of the normally open contact of the HAND side of the HOA, wire H13 and H14)
c). Verify voltage on terminal 1 (Verify the jumper between terminals 2 and 1 is secure, if the has been remove, verify the circuit wired between the terminals 2 and 1 is closed)
d). Verify voltage on terminal 2 (No voltage on terminal 2 verify Fuse (FU1) on the secondary side to the transformer is not blown.
e). If the fuse (FU1) is not blown, verify voltage on the primary and secondary side to the transformer (verify fuses FU2 and FU3 are not blown and then check the power supply to the cabinet.)
 
              2)   Is the RCR relay energized with the HOA switch in the Auto position? NO
 a). Voltage should be present on Terminal 6 (There is an external auto start contact on terminals 6 and 7 supplied by the end user and verify the contact is closed)
 b). Verify voltage on terminal 7 (Verify HOA is in AUTO position and voltage is present on both sides of the normally open contact of the AUTO side of the HOA, wire A13 and A14)
c). Verify voltage on terminal 1 (Verify the jumper between terminals 2 and 1 is secure, if the has been remove, verify the circuit wired between the terminals 2 and 1 is closed)
 d). Verify voltage on terminal 2 (No voltage on terminal 2 verify Fuse (FU1) on the secondary side to the transformer is not blown.
 e). If the fuse (FU1) is not blown, verify voltage on the primary and secondary side to the transformer (verify fuses FU2 and FU3 are not blown and then check the power supply to the cabinet.)

Symmetra LX Spare Parts List




Issue

Where can I find a list of commonly replaced spare parts for the APC Symmetra LX UPS system?



Product Line

Symmetra LX



Environment

All serial numbers



Cause

The purpose of this document is to provide a user with a list of spare parts for servicing a Symmetra LX UPS.  If parts not listed are required, please contact technical support for assistance.


Resolution

 
Spare parts for 208/240 VAC Symmetra LX systems (Symmetra system part numbers ending in "P" or "PXR")
 
 
Power Module
 
  • Symmetra LX 4 kVA Power Module, 200V/208V - SYPM4KP


Battery Modules
 
  • APC Symmetra LX Battery Module - SYBT5
  • APC Symmetra LX Battery Module with flame retardant case (used primarily in Japan) - SYBT5FR


Intelligence Modules
 
  • APC Symmetra LX Intelligence Module - SYMIM5
 
 
Rack-Mounting Hardware 
 
  • Symmetra LX Four-Post Rack-Mounting Rails - SYAOPT1 
  • Symmetra LX/Symmetra RM Two-Post Rail Kit - SYOPT12 
 
 
Mainframe Parts and Accessories 
 
  • Symmetra LX frame electronics module – 200V/208V - SYAFSU13 
  • Symmetra LX Input/Output wiring tray – 200V/208V - SYAFSU14 
  • Symmetra LX Communications Card - SYAFSU15 
  • Symmetra LX 13 U replacement door - SYAFSU2 
  • Symmetra LX 19 U replacement door - SYAFSU3 
  • Symmetra LX 32 U replacement door - SYAFSU5 
  • Symmetra LX Castor kit - left front, right rear - SYAFSU6 
  • Symmetra LX Castor kit - right front, left rear - SYAFSU7 
  • Symmetra LX top panel - SYAFSU8 
  • Symmetra LX 13 U left side panel - SYAFSU9L 
  • Symmetra LX 19 U left side panel - SYAFSU10L 
  • Symmetra LX 32 U left side panel - SYAFSU12L 
  • Symmetra LX 13 U right side panel - SYAFSU9R 
  • Symmetra LX 19 U right side panel - SYAFSU10R 
  • Symmetra LX 32 U right side panel - SYAFSU12R


 
Extended Run (XR) Frame Parts and Accessories
 
  • APC Symmetra LX XR Communication Card - SYAFSU16 (used in Symmetra LX branded XR frames - SYAXRxxxx, SYARMXRxxxx, SYBFxxxx)
  • APC Symmetra RM XR Communication Card - SYXRCC (used in Symmetra RM branded XR frame - SYRMXR4)
  • APC Symmetra LX XR Communication Cable - 0W6002B
  • APC Symmetra LX 5U replacement door - SYAFSU1
 
 
 
For 220/230/240/380/400/415 VAC Symmetra LX systems (Symmetra system part numbers ending in "I" or "IXR")
 
 
Power Module
 
  • Symmetra LX 4 kVA Power Module, 220V/230V/240V - SYPM4KI


Battery Modules
 
  • APC Symmetra LX Battery Module - SYBT5


Intelligence Modules
 
  • APC Symmetra LX Intelligence Module - SYMIM5


Rack-Mounting Hardware 
 
  • Symmetra LX Four-Post Rack-Mounting Rails - SYAOPT1 
  • Symmetra LX/Symmetra RM Two-Post Rail Kit - SYOPT12 
 
 
Mainframe Parts and Accessories 
 
  • Symmetra LX frame electronics module – 230V - SYAFSU13I 
  • Symmetra LX Input/Output wiring tray – 230V - SYAFSU14I
  • Symmetra LX Communications Card - SYAFSU15 
  • Symmetra LX 13 U replacement door - SYAFSU2 
  • Symmetra LX 19 U replacement door - SYAFSU3 
  • Symmetra LX 32 U replacement door - SYAFSU5 
  • Symmetra LX Castor kit - left front, right rear - SYAFSU6 
  • Symmetra LX Castor kit - right front, left rear - SYAFSU7 
  • Symmetra LX top panel - SYAFSU8 
  • Symmetra LX 13 U left side panel - SYAFSU9L 
  • Symmetra LX 19 U left side panel - SYAFSU10L 
  • Symmetra LX 32 U left side panel - SYAFSU12L 
  • Symmetra LX 13 U right side panel - SYAFSU9R 
  • Symmetra LX 19 U right side panel - SYAFSU10R 
  • Symmetra LX 32 U right side panel - SYAFSU12R
 

Extended Run (XR) Frame Parts and Accessories
 
  • APC Symmetra LX XR Communication Card - SYAFSU16 (used with Symmetra LX branded XR frames - SYAXRxxxx, SYARMXRxxxx, SYBFxxxx)
  • APC Symmetra RM XR Communication Card - SYXRCC (used with Symmetra RM branded XR frame - SYRMXR4)
  • APC Symmetra LX XR Communication Cable - 0W6002B
  • APC Symmetra LX 5U replacement door - SYAFSU1