Win a $4,000 Switchboard Upgrade
Learn How
plate only 3gang arch

Switch Plates Standard Range, Architrave Size, 3 Gang

Catalogue Number: 33
plate only 3gang arch
Colour White Electric (WE)
  • White Electric 1 PCE 1

Specifications

hide show
Range of product
Standard Series
Product brand
Clipsal
Number of gangs
3 gangs
Product destination
switch
Fixing mode
by screws
Material
plastic
Marking
without marking
Mounting position
horizontal and vertical
Fixing center
97 mm
Length
112 mm
Width
32 mm
Depth
11 mm
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Weight
20 g
Package 1 Height
35 mm
Package 1 width
12 mm
Package 1 Length
115 mm
Sustainable offer status
Green Premium product
EU RoHS Directive
Compliant
Mercury free
Yes
RoHS exemption information
Yes
China RoHS Regulation
Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure
ENVPEP120506EN

Frequently Asked Questions

hide show

What is the 600 series 3 gang switch that the switches are in a pyramid configuration?

That is the PDL683VWP, Waterproof switchplate (IP56)
They can be found on page 33 of the 2014 PDL Pocketbook.

Why is my Conext CL showing an alarm code: 32 & 33 - AC temp snsr flt & DC temp snsr flt ( AC and DC Temp Sensor Fault Service Alarm)

Issue: 
Customer is calling to confirm alarm code: 32 & 33 ( AC temp snsr flt Service)

Product Line: 
Conext CL 18000NA Conext CL 25000NA Conext CL 20000E Conext CL 25000E

Environment:  
On site troubleshooting
 
Cause:
Abnormal ambient temp
Cooling problem
Detection circuit malfunction

Resolution: 
Check fans, installation conditions, air inlet and outlet
Check Internal temperature displays in STATUS screen
Turn off and on AC breaker
If failure persists, replace the unit

What is the server/client side requirement of Citect Anywhere?

Server-side requirements:-

• Windows Server OS
• Microsoft Remote Desktop Services (RDS) CALs
• Vijeo Citect / CitectSCADA v7.20 (SP5) and above
• Citect Control/View Only Client licenses
• Citect Anywhere licenses 

Client-side requirements:- 

Any operating system with the HTML5-capable browser
  • Internet Explorer® 10 or higher
  • Safari® 8 or higher
  • Chrome™ 33 or higher
  • Microsoft® Edge

Why does ATS48 not operate when wired like the recommended diagram on page 74 of the June 2002 manual?

The user's manual recommended diagram on page 74 is incorrect for proper operation.  
On line 2 of the ladder diagram after fault relay R1A to R1C connection the coil that is labeled TR for trip relay should be a FR coil for fault relay.
Then should add a line after this that has a NC (normally closed ) FR ( fault relay ) contact in series with a TR ( trip relay ) coil.

This configuration would then allow proper operation of unit.

What is the part # for a clear plastic bezel for a ZB4BW31, ZB4BW32, ZB4BW33 ZB4BW34, ZB4BW35, ZB4BW36, ZB4BW37 ?

Issue:
What is the part # for a clear plastic bezel for a ZB4 illuminated push buttons (incandescent type)?

Product Line:
Push Buttons and Operator Interface

Environment:
ZB4 Illuminated push buttons

Cause:
Product selection

Resolution:
Use a W415595280111

Does an EGX100 or EGX300 have a fiber optic connection port?

Issue:
A user would like to connect to an EGX gateway via a fiber optic connection.
 
Product Line:
EGX100
EGX300
 
Cause:
A user requires a fiber optic connection to the EGX gateway.
 
Resolution:
The EGX100 and EGX300 gateways do not have an on board fiber optic port therefore a direct fiber optic connection to the gateway is not possible.

Alternate Option: 
A user can purchase and EGX in a Factory Assembled enclosure that contains a (4-Copper & 1-Fiber) Ethernet switch. The enclosure can be purchased for indoor or outdoor use.
 
Please reference page 33 of the attached factory assembled enclosure selection guide for part numbers. 
Show More