What is the AC3 rating of the LC1D18***
The rating is 18A
What is the part number for 238A with 25mm spout?
The 238/25 has 1 x 25 mm spout & 2 x25 mm conduit entries.
What is the coil consumption or burden for the Tesys LC*D** contactors?
* 1 or 2
** 09 through 38
Issue:
Coil consumption or burden for the Tesys LC1D/2D contactors from 9A - 38A
Product Line:
Contactors and Starters - IEC
Environment:
North American Products
Resolution:
All AC coils for the LC1D09 through LC1D38 3-pole contactors ( including ring tongue, quick connect and spring terminal versions ) have an inrush of 70 volt-amps for either 50 or 60 Hertz applications, and a sealed value of 7 volt-amps for 50Hertz applications or 7.5 volt-amps for 60 Hertz applications.
Where can I find the ASB230501 Data Sheet?
Attached is the ASB230501 Data Sheet.
Is there a 35A double pole mechanism?
No. We have 30M35 which is 1 pole, 35A mech.