SURROUND 2 GANG HORIZONTAL SATURN
SURROUND 2 GANG HORIZONTAL SATURN
SURROUND 2 GANG HORIZONTAL SATURN
SURROUND 2 GANG HORIZONTAL SATURN

Surround Socket Outlet Saturn - Horizontal - 2-gang - White Electric

Catalogue Number: 4000H2
SURROUND 2 GANG HORIZONTAL SATURN
SURROUND 2 GANG HORIZONTAL SATURN
SURROUND 2 GANG HORIZONTAL SATURN
SURROUND 2 GANG HORIZONTAL SATURN
Colour: White Electric
Colour: Per UOM Std.
  • Black 1 PCE 1
  • White Electric 1 PCE 1

Specifications

hide show
Range of product
Saturn Series 4000
Product brand
Clipsal
Mounting position
horizontal
Sustainable offer status
Green Premium product
REACh Regulation
Free of Substances of Very High Concern above the threshold
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
Environmental Disclosure
ENVPEP121018EN
Circularity Profile
N/A

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Product Brochures

  • Installation Instruction

  • Product Environmental

  • Specifications

  • Certificates (MSDS)

Frequently Asked Questions

hide show

What is the mounting frame for the 4025H2

 Part code is 4000H2

What is the Cut-Out, Dimensions and/ or Template for a 4000VH2 quad surround?

Please see the below image for the Dimensions and/ or Template for a 4025H2 quad outlet.

How do I scale 0 - 4095 to 6400 - 32000 using 984 Ladder Logic?

The following network scales data from 0-4095 to 6400 - 32,000 when 4-20ma (6400 = 4 mA, 32,000 = 20 mA) outputs are required
but a 0-20ma analog output is used. .





Register 400001 and 400002 are used together in the top node of the EMTH Block, where 400001 is
always 0000 data and 400002 is the variable data, 0-4095, to be scaled. Register 400003, displayed in data
format float, is a fixed floating point value that the user enters as 6.25153 (note that two registers are
used to create the floating point value, 400003 & 400004 in this example). Register 400005 (and 400006)
is the floating point result of the integer and floating point multiplication (EMTH block).





The FTOI (Floating Point TO Integer) block converts the floating point result of registers 400005
and 400006 to an integer value in a single register 400007.

The AD16 block adds the top node register 400007 to the middle node constant 6400 and places
the result in register 400009. This register will then map to one of the analog outputs.

The following data screens shows the input values of 0 and 4095 and there corresponding results.





Is there a decorative surround for the 4025H2 quad outlet?

Yes the part number for a decorative surround for the 4025H2 quad outlet is a 4000H2.

How do I scale data from 0-32,000 to 0-4095 using 984 Ladder Logic?

 

The following network scales data from 0-32,000 to 0-4095 for use with analog signals.





 
Register 300001 contains the analog input data (0-32,000).

This data gets BLKM (Block Moved) to register 400002. 

Registers 400001 and 400002 are the top integer nodes of an EMTH (Divide Integer by Floating point) which is divided by registers 400003 and 400004 (display 400003 as data type float), the middle node registers that contain the floating point constant (7.814408).  

The floating point result is found in registers 400005 and 400006 that is then converted by the FTOI
(Floating point TO Integer) Block to register 400007.

Starting Register number in Modbus Read functions

Goals and Symptoms

When performing Modbus read commands, it is important to apply the right starting register address in the read function. Otherwise, the wrong register will be accessed from the meter, giving unexpected data for the meter parameter being read.


  • Meter is functioning as expected. The front panel values for voltages and currents are within expected ranges for the system being monitored. However, modbus read functions from a master station (e.g. a PLC) give values that do not correspond to the front panel values.

Facts and Changes

Modbus, modbus rtu, function read, modbus map, holding register, staring register, function 03, modbus read packet

Causes and Fixes

Cause
One probable cause would be that, the modbus function read command is not pointing to the right registers. The modbus protocol requires an offset to be introduced in the starting register address when reading the slaves register.

Resolution

When reading the meter parameters, the Master must send the device a Read Holding Registers packet. This packet must specify a start register and the number of registers to read. When the function read is received, the slave responds with a packet containing the registers in the range defined in the read request.

However, consider the 3710 Modbus map, which states that according to the MODBUS protocol, in response to a request for address 4xxxx, the master reads register xxxx-1 from the slave (3710). For example, a request for register 40011 returns register 10 from the slave.

What does the above statement mean? Why is an offset required?

Holding registers, by default, are defined the 4xxxx range, the first holding register staring at 40001. The starting register in the read packet is, on the other hand, numbered from zero. Hence, the start register zero automatically points to holding register 40001, starting register one points to holding register 40002, etc. The fact that the first holding register is 40001 and not 40000 explains the offset that needs to be introduced in the starting register number.

Hence, considering the 3710 Modbus Map statement, if the Master needs to read register 40011, then the corresponding starting register that needs to be put in the read function would be 10 (0A hex) since register 40011 is the register 10 from the first holding register, 40001:
40001 > Start register 0
40002 > Start register 1
40003 > Start register 2
40004 > Start register 3
40005 > Start register 4
40006 > Start register 5
40007 > Start register 6
40008 > Start register 7
40009 > Start register 8
40010 > Start register 9
40011 > Start register 10

The Modbus Read Request Packet for a master reading 3 registers from a slave with unit ID 100 (64 Hex) and for starting register of 40011 should be:
 

Slave ID
Function
Start Register (40011)
# of Registers
CRC Checksum
64
03
00
0A
00032C3C


To summarize, when looking at a modbus map, the starting register number to be used in the read function:

Start Register = Modbus Register 40001.

 

Original article#12774

Public

All content © 1992-2007 Schneider Electric


Legacy KB System (APS) Data: RESL188799 V1.0, Originally authored by KBAdPM on 11/03/2007, Last Edited by KBAdPM on 11/03/2007
Related ranges: Modbus / JBus

Can you get a plate larger than 6 gang in the 2000 series?

Not directly, but using the 2000/2 or 2000h2 series you can fit 2 plates under one surround.

What are the dimension for the 2000H2?

The dimension for the 2000H2 are - H232mm x W 76mm x D13mm

For further information , visit link below:-
https://www.clipsal.com/Trade/search-results?q=2000H2
User-added image

When using Concept, what may cause a 4000h Stop Code on my Momentum I/O Bus CPU?

The 4000h stop code may be generated by a bad I/O map, extended memory error or missing loadable. This error will also occur when a Momentum I/OBus network has a third party Interbus device on the network but undefined. The Concept ModConnect tool must be used to generate a MDC file that will define the module and allow the Concept database to insert this definition in the I/O map configuration. A common symptom of this problem is the program will download and start with no problems with an older computer that has the MDC definitions installed. When the project is moved to another computer without the modules MDC file, the project will report a 4000h error after download/ start. To eliminate this error generate a new MDC file using the Concept Modconnect tool.


Can I tell what the Modbus Plus address of my Modicon PLC is via 984 ladder logic?

Yes, the contents of the address configured in node 2 of the MSTR Instruction Function Code #3 (Get Local Statistics) will give you the Modbus Plus Network address of the PLC.
Below is a example of a MSTR Instruction using Function Code #3 (Get Local Statistics) to get the Modbus Plus address of the PLC

400001 = 3 (Operation Type)
400003 = 1 (length)
400004 = 2 (Offset)
400010 = 2 (Network address of this station)

How can a floating point value be moved into 4XXXX registers in a Quantum PLC with 984 LL?


A floating point value can be moved into 4XXXX registers with the equation network. An example of moving a floating point value of 123.456 into registers 40001 and 40002 is shown below:

 

Do the 4000PP suit both the Saturn and Saturn Zen ranges?

Yes, the 4000PP will cover bother ranges.

For more information, please refer to the link:
https://www.clipsal.com/Trade/Products/ProductDetail?catno=4000PP

Do we make a 4000VH1 for saturn architrave?

Unfortunately no we don't.

Is there a wall box for a 2025H2?

The wall box for the 2025H2 is the 2157H2.

Some of the key features are:
  • 2 gang
  • 84 mm (2 sets)
  • With sliding nuts for accurate alignment of accessory
  • Precision stamped from 0.9 mm strip bright electrogalvanised, for 2000H2 series

For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=2157H2

 

What is the bracket to suit 4025H2?

The plaster bracket to suit 4025H2 is 2155PHRM2.

How to manually set the clock in a Modicon PLC using Concept software?

Goals and Symptoms

The Time of Day clock in a Modicon PLC consist of 8 registers. The steps below explains how to manually set the clock on the Modicon PLC should you want to synchronize the PLC clock with a HMI or SCADA.

Causes and Fixes


Hardware:
Modicon 984
Quantum
Momentum
Compact

Software:
Modsoft
Proworx PLUS/NXT/32
Concept
 

1)From the Control Register 4x

  • Enter 0000h. This will stop the clock from being updated

 

2) Set the TOD registers 4x + 1 to 4x + 7 to the correct time.

 

3) From the Control Register 4x, enter 8000h (This sets bit 1, Clock value are being set).
If successful, the control Register should display 2000h,

4) From the Control Register 4x

  • Enter 4000h (This sets bit 2, Clock values are being read)
    If successful, the control Register should display 2000h

What is the part number for Saturn paint covers?

4000PP-TR ( sold as a pack of 250)

Will the 4000VH1 cover the grid in ZEN Plates?

Yes - It will cover the grid so that you cannot see the black coloring.
 

What is a 585OF

585OF are mounting frames like the 4000VH1 but for CBUS Saturn range

Does the 4000VH1 Fit the Zen range?

The decorative surround 4000VH1 will Fit the Zen range.

 

For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=4000VH1

 

Accutech Modbus Register Mapping

Modbus RTU protocol is supported on the BR10 and BR20 Base Radios. Transmission rates of 9600, 19200, 38400, 57600, 115200 are supported with even, odd or no parity, 8 data bits and 1 or 2 stop bits. The Modbus settings are configured by using the push buttons on the base radio only. The BR10 contains 1 RS-485 port for Modbus communications. The BR20 contains 1 RJ45 connection called the "Short Haul Data" port. This port can be configured for 2-wire RS-485 or 3-wire RS-232 by a dipswich next to the serial port.

The following menu items are used to configure Modbus in the base radio via the push buttons. For a complete menu map of all Accutech Instruments, please reference the Accutech Wireless User Manual that is installed along with Accutech Manager Software an your PC.

BAUD RT - Baud Rate
DEV ID - Modbus Device ID
PARITY - Parity
STOPB - Stob bit selection
MODMAP - Register mapping options (see below)
MODADR - Modbus address of base radio
ORDER - Floating point word order

There are two user options to determine Modbus mapping in the base radio/field units. The MODMAP configuration determines if the mapping will be DEV mode (Device ID) or REG mode (Register)

Device ID Mode

  • Poll for individual devices (Base Radio and Field Units)
  • Modbus Station ID = Base Radio Modbus Station Address + Field Unit RF ID
  • Modbus starting register = 40001

Register Mode

  • Poll single Modbus station ID for complete Accutech network
  • Modbus Station ID = Base Radio Modbus Station Address
  • Field unit Modbus address are multiples of their RF ID
  • Modbus starting register = (Field Unit RF ID * 10) + 40001

Base Radio Registers

Base Radio Holding Register (Device and Register Mapping Modes)

Device ID: 1 To 247 Max.

Address

Description

Register Type

40001

Base Radio Device Type

16-Bit Unsigned Integer

40002

Base Radio Device Status

16-Bit Unsigned Integer

40003

Number of Field Units Expected on the wireless network.

16-Bit Unsigned Integer

40004

Number of Field Units actually online in the wireless network.

16-Bit Unsigned Integer

40005

Online/Offline Status Of Field Units with RFIDs 1-16

16-Bit Unsigned Integer

40006

Online/Offline Status Of Field Units with RFIDs 17-32

16-Bit Unsigned Integer

40007

Online/Offline Status Of Field Units with RFIDs 33-48

16-Bit Unsigned Integer

40008

Online/Offline Status Of Field Units with RFIDs 49-50

16-Bit Unsigned Integer

40009

Diagnostic Counter (increments each second)

16-Bit Unsigned Integer

40010

Reserved For Future Use

16-Bit Unsigned Integer

 

Field Unit Holding Registers

Field Unit operational data is stored in a sequential block of 10 Modbus registers in the Base Radio. The Modbus Station address and the actual register addresses will vary depending on the Modbus Mapping mode set in the base radio. The Modbus Station address and register locations are described below for each Mapping mode.

Device ID Mapping Mode

When DEVMODE is selected, the base radio stores the field unit and base radio operation data (10 Modbus holding registers) in separate Modbus Station addresses. In this mode, the SCADA Host (Modbus Master) needs to send an individual poll request for each field units data and the base radio data. Station addresses are determined using Base Radio Device ID parameter and the Field Units RFID parameter. This mode is suitable for systems using a template for each field unit.

Field Unit Modbus Station Address = Base Radio Device ID + Field Unit RFID

Field Unit Holding Register Addresses

Field Unit Register Description

Register Type

40001 and 40002

Device Type

Two Modbus registers formatted as a 32-Bit IEEE Floating Point1

40003 and 40004

Device Status

Two Modbus registers formatted as a 32-Bit IEEE Floating Point1

40005 and 40006

Primary Sensor Value2

Two Modbus registers formatted as a 32-Bit IEEE Floating Point1

40007 and 40008

Secondary Sensor Value2

Two Modbus registers formatted as a 32-Bit IEEE Floating Point1

40009 and 40010

Tertiary Sensor Value2

Two Modbus registers formatted as a 32-Bit IEEE Floating Point1

1The default floating point format for Modbus database registers is Low Word, High Word. For example if a floating point value is in registers 40001 and 40002 then 40001 is the low word and 40002 is the high word. For SCADAPack controllers 40001 is the high word and 40002 is the low word. The floating point word order is decided by Modbus Floating Point Order of base radio Modbus Communication Configuration.

2Any field unit that is currently offline will return NaN (Not a Number) when queried for its primary, secondary or tertiary measurement value. If a field unit is online, NaN will also be returned for measurement values that do not exist in the device. For example, a field unit providing one measurement will return NaN for its secondary and tertiary values.

Register Mapping Mode

 When REGMODE is selected, the base radio stores the field unit and base radio operation data (10 Modbus holding registers) in sequential blocks of registers located at a single Modbus Station address. The base radio uses register addresses 1 through 10 with subsequent groups of 10 registers used by each field unit. Station address is determined by the base radio Device ID and the Register addresses for each field unit are offset from the base radio registers by a factor of 10 times the field unit RFID parameter. This mode is suitable for a system that wants to poll for multiple field unit devices at once.

Field Unit Modbus Station Address = Base Radio Device ID

Field Unit Holding Register Addresses

Field Unit Register Description

Register Type

40001 + (RFID * 10) and 40002 + (RFID * 10)

Device Type (see list below)

Two Modbus registers formatted as a 32-Bit IEEE Floating Point1

40003 + (RFID * 10) and 40004 + (RFID * 10)

Device Status (see list below)

Two Modbus registers formatted as a 32-Bit IEEE Floating Point1

40005 + (RFID * 10) and 40006 + (RFID * 10)

Primary Sensor Value2

Two Modbus registers formatted as a 32-Bit IEEE Floating Point1

40007 + (RFID * 10) and 40008 + (RFID * 10)

Secondary Sensor Value2

Two Modbus registers formatted as a 32-Bit IEEE Floating Point1

40009 + (RFID * 10) and 40010 + (RFID * 10)

Tertiary Sensor Value2

Two Modbus registers formatted as a 32-Bit IEEE Floating Point1

 

1The default floating point format for Modbus database registers is Low Word, High Word. For example if a floating point value is in registers 40001 and 40002 then 40001 is the low word and 40002 is the high word. For SCADAPack controllers 40001 is the high word and 40002 is the low word. The floating point word order is decided by Modbus Floating Point Order of base radio Modbus Communication Configuration.

2Any field unit that is currently offline will return NaN (Not a Number) when queried for its primary, secondary or tertiary measurement value. If a field unit is online, NaN will also be returned for measurement values that do not exist in the device. For example, a field unit providing one measurement will return NaN for its secondary and tertiary values.

What is the Run Current and In-Rush current for FLS50LED, LED slimline floodlight 50W 4000K?

FLS50LED has the below details 

-Run current: 0.249A 
-In-rush current: 15A 

Datasheet attached for further reference. 


 

The “Generic Modbus” application does not provide status bits values in binary

Issue:
The “Generic Modbus” application does not provide status bits values in binary

Product line:
Generic Modbus Application or Similar application


Environment:
Generic Modbus Application or Similar application


Cause:
The “Generic Modbus” application does not provide status bits values in binary


Resolution:
Take the value provided by the application and convert it to binary by using a calculate like the one provided by Windows.  If using the Windows calculator, you may have to change the calculator to scientific or Programmer mode to accomplish this conversion.

Below is a couple of examples from a Galaxy VX:

Example 1:  Register 400002 (16385)

16385 in BIN 100 000 0000 0001

This example has 14 bits and to get to 16 bits two zeros were added to the left (red text)

10 0000 0000 0001 is 0010 0000 0000 0001

 

Example 2:  Register 400010 (512)

512 in BIN 10 0000 0000

This example has 10 bits so six bits needs to be added to the left (red text)

10 0000 0000 is 000 0010 0000 0000



The “Generic Modbus” application does not provide status bits values in binary

Issue:
The “Generic Modbus” application does not provide status bits values in binary


Product line:
Generic Modbus Application or Similar application


Environment:
Generic Modbus Application or Similar application


Cause:
The “Generic Modbus” application does not provide status bits values in binary


Resolution:
Take the value provided by the application and convert it to binary by using a calculate like the one provided by Windows.  If using the Windows calculator, you may have to change the calculator to scientific or Programmer mode to accomplish this conversion.
Below is a couple of examples from a Galaxy VX:
Example 1:  Register 400002 (16385)
16385 in BIN 100 000 0000 0001
This example has 14 bits and to get to 16 bits two zeros were added to the left (red text)
10 0000 0000 0001 is 0010 0000 0000 0001
 
Example 2:  Register 400010 (512)
512 in BIN 10 0000 0000
This example has 10 bits so six bits needs to be added to the left (red text)
10 0000 0000 is 000 0010 0000 0000

 

Is Silver color on part 2000/2 same as Brushed Aluminium?

The Silver color is shinier than Brushed Aluminium and is distinctly different

for information on this part please refer to https://www.clipsal.com/Trade/Products/ProductDetail?catno=2000/2

User-added image

Will there be a Saturn with a white back instead of black

No - You will need to use the mounting frames 4000VH1

What is the white surround for the saturn series?

The part number is 4000VH1

Does the 4000VH1, Saturn surround, come in Pure White?

The 4000VH1 comes in basic Bakelite colours. White Electric, Black, Cream, Desert Sand and Soft Grey.
Please see following link for more information on Saturn Parts
https://www.clipsal.com/Trade/Products/ProductDetail?catno=4000VH1

Is the 4025H2 just a standard 4025 behind the cover plate?

Yes the 4025H2 just has a standard 4025 behind the cover plate.
Some of the key features are:

  • Saturn 4000 series
  • 4 Gang
  • 10A
  • 250V AC

For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=4025H2

​How to read Modbus Status bits

Issue:
How to read Modbus Status bits

 

Product line:
All products


Environment:
All products


Cause:
How to read Status bits



Resolution:
Using a Modbus tool like Generic Modbus Tester you receive the values in the two examples below.  The Generic Modbus tester does not provide binary values so the examples below shows the conversion.  If the application used provides binary then keep that part.

 

Below is a couple of examples from a Galaxy VX:

Example 1:  Register 400002 (16385)

16385 in BIN 100 000 0000 0001

This example has 14 bits and to get to 16 bits two zeros were added to the left (red text)

10 0000 0000 0001 is 0010 0000 0000 0001

Below is the mapping of the bits to the Modbus registers to the Galaxy VX.  You start the with zero on the right and end with 15 on the left.


 

Example 2:  Register 400010 (512)

512 in BIN 10 0000 0000

This example has 10 bits so six bits needs to be added to the left (red text)

10 0000 0000 is 000 0010 0000 0000

Below is the mapping of the bits to the Modbus registers to the Galaxy VX.  You start the with zero on the right and end with 15 on the left.

Modbus; How to read Status bits

Issue:
Modbus; How to read Status bits


Product line:
All products


Environment:
All products


Cause:
How to read Status bits


Resolution:
Using a Modbus tool like Generic Modbus Tester you receive the values in the two examples below.  The Generic Modbus tester does not provide binary values so the examples below shows the conversion.  If the application used provides binary then keep that part.
 
Below is a couple of examples from a Galaxy VX:
Example 1:  Register 400002 (16385)
16385 in BIN 100 000 0000 0001
This example has 14 bits and to get to 16 bits two zeros were added to the left (red text)
10 0000 0000 0001 is 0010 0000 0000 0001
Below is the mapping of the bits to the Modbus registers to the Galaxy VX.  You start the with zero on the right and end with 15 on the left.


 
Example 2:  Register 400010 (512)
512 in BIN 10 0000 0000
This example has 10 bits so six bits needs to be added to the left (red text)
10 0000 0000 is 000 0010 0000 0000
Below is the mapping of the bits to the Modbus registers to the Galaxy VX.  You start the with zero on the right and end with 15 on the left.




 

What is the plaster bracket to suit the 2000/2?

The part number for the plaster bracket to suit the 2000/2 is 2155PRM/2.

Is there a 4 gang GPO in the Medilec range?

No there isn't but you can put 2 x doubles in a double surround - 2000H2, making 4 GPO's in total.

What is the Cut-Out, Dimensions and/ or Template for a 4025H2 quad outlet?

Please see the below image for the Dimensions and/ or Template for a 4025H2 quad outlet.

What can I use to hide the black grid on a Clipsal 4061TD one touch dimmer & cover

 You can use a 4000VH1 to hide it

STB Module Information Availability via CAN Fieldbus

Goals and Symptoms

The purpose of this resolution is to point out that STB module diagnostic information can be read over the CAN fieldbus.

Facts and Changes

By default, 400xh objects are in the exported CAN .eds file created in Advantys Configuration Software. They are not displayed in the ACS island fieldbus image. They may be selected from the exported file in Sycon.and added to the .co file.
For instance:

Index 4004h will display a 1 for the module removed from an island.
Index 4005h will display a 1 indicating a module status register error.

In Advantys Configuration Software on-line Hardware Help for the CAN NIM, you can find 400x object descriptions under Fieldbus Communication Support.

re:

Causes and Fixes

See Facts and Changes for information.


Legacy KB System (APS) Data: RESL190503 V1.0, Originally authored by WeDa on 12/29/2007, Last Edited by WeDa on 12/29/2007
Related ranges: Advantys STB

What is the frequency of the internal buzzer used in the Magelis XBTGT 2000 to 7000 series HMI terminals?


The buzzer frequency is between 2000Hz and 2600 Hz. (2300Hz typical)


Legacy KB System (APS) Data: RESL192877 V1.0, Originally authored by MiMe on 10/01/2008, Last Edited by MiMe on 10/01/2008
Related ranges: Magelis XBT G

What is the replacement lamp for a EXITSM?

Unfortunately we do not sell these as spare part you will need to seek a different manufacturer such as osram etc.

The specs are a 4000K, 1.2 Watt LED Tube.
Highly efficient LED lamp: The fitting is equipped with a 1.2W LED tube which provides longer life and lower power consumption.

What mounting options can be used with 4025H2 or Z4025H2 ?

Use a 2154H2 ( wall clip) , 2155PHRM2 ( plaster mount bracket ) or 2157H2 ( Wall box) recessed 8mm
for more information on this product range please visit the Clipsal web site on the link provided
https://www.clipsal.com/Trade/search-results?q=4025h2

Can I poll 6 Digit Modbus registers with Telepace Studio?

The MSTR and MSIP use a block of registers to store their configurations.

If the MSTR block uses register 41001 in the SCADAPack as it's configuration start register, then :

41001 = Comm port number

41002 = function code

41003 = slave controller address

41004 = slave register address

41005 = master register address

41006 = length

41007 = time out in 0.1s increments

Trying to configure the MSTR block in Telepace prevents you from putting in a slave register address greater than 49999.

Using a PUTU block, you can put an unsigned integer in the range 40001-65535 into register 41004 to indicate the slave register address. It appears as though the program will take the value in register 40004 and subtract 40001 to determine the holding register offset that gets sent in the actual modbus message.

For example, using PUTU to put a value of 50010 into register 40004 would then cause the MSTR block to poll for a holding register with an offset of 10009 in the message which would correspond with a 6 digit address of register 410010.

The largest unsigned integer you could put into register 40004 would be 65535, which would correspond with a 6-digit modbus holding register of 425535.



 

Does PowerLogic SCADA support waveform data of ION meters?

No, Powerlogic SCADA (PLS) currently does not support the waveform data from ION meters; valid through PLS v7.10 SR3.
Waveforms from the following devices are currently supported as of v7.10 SR3: Circuit Monitor 3000s, Circuit Monitor 4000s, Power Meter 800s, and Sepam 20s, 40s, and 80s.


Legacy KB System (APS) Data: RESL200266 V2.0, Originally authored by KBAdPM on 10/16/2009, Last Edited by MaTh on 12/01/2010
Related ranges: PowerLogic SCADA 7.1

What is the size of the inter conductor for the N-series recloser cables (38kV)?

This size will vary depending upon the rating of the conductors:


  • 1. 250A 80mm2
    2. 340A 120mm2
    3. 400A 180mm2
    4. 630A 240mm2
    5. 800A 400mm2

    These are shown in more detail in the attached guide.

    Olex cables.pdfOlex cables.pdf


Legacy KB System (APS) Data: RESL212274 V1.0, Originally authored by DaFr on 08/09/2013, Last Edited by DaFr on 08/09/2013
Related ranges: Others protection relays

Configuring Concept I/O Scanning for ZBRN1 Receiver

After setting the IP address
Set the UNIT ID to 255
Read Ref Slave to 400001
Read Length to 4    (This will read 4 16 bit registers)
Read Ref Master to a location on the PLC ex. 400100

This will write to 400100, 400101, 400102 & 400103

Can you get a 2000/2 in chrome.

This part  only comes in standard 'bakelite' colours. Please visit the below link to our website for more information and colour options.
Today, the 2000 series is clipsal’s most popular product range and its surrounds are available in a wide choice from single gang standard size versions to multigang surrounds for situations where you want to house up to four gridplates in a single surround. 2000 series flush surrounds feature a design that neatly conceals all mounting holes, a durable high gloss finish for easy cleaning and a clever clip on/clip off design that enables surrounds to be easily removed when redecorating to conceal overpainting or untidy cut marks when wallpapering.
Please see following link for more details and colour choices of multi gang range.
https://www.clipsal.com/Trade/Products/ProductDetail?catno=2000/2

What is the part number of Mounting bracket for a 2000/2?

The part number for a for a mounting bracket for a 2000/2 is 2154/2.

Some of the key features are:
  • Mounting brackets
  • 2 gang
  • For plaster board or hardboard mounting for wall boards up to 12 mm thick

For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=2154/2
 

What is the Colour Light output (CCT) of the CLIFLS20LED Floodlight

The output CCT is 4000K

Adding the 170ADM85010 and 170ADO83030 I/O bases to the module pick list in Concept.

Goals and Symptoms

The purpose of this resolution is to illustrate the steps necessary to add the 170ADM85010 and 170ADO83030 I/O bases.

Causes and Fixes

The attached MDC files will be needed to add these modules. Put the MDC files in the Concept root directory and remove the .txt file extension.
Once this is done, launch the ModConnect Tool from the Programs menu as seen below:
.
Once the ModConnect tool is running, Choose "Open Installation File"
.
Choose the appropriate MDC file from the window shown below:
.
The next window will allow the user to choose which modules are added. Choose "Add All"
..
The tool will then show the added modules:
.
The tool can be closed. When Concept is launched, these bases will be available from the pick list for Momentum bases.

NOTE: This procedure must be done on every computer where the project will be used. If it is not done on a computer where the project is used, the Momentum controller will not run the project and will come up with a 4000h error code.

The customer wanted a cut-out template for the quad power point 4025H2?

Please see attached for the cut-out.

For further information on the saturn series quad power point 4025H2 please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=4025H2
 

What is the part number for the surround that fits a 4025H2?

The part number for the surround that fits a 4025H2 is 4000H2.

For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=4000H2

 

What is part number for Saturn Quad GPO in Horizon Black?

The part number for Saturn Quad GPO in Horizon Black is a 4025H2 -HB.
Show More