BC lampholder adaptor

White Electric | BC lampholder adaptor

BC lampholder adaptor

Item Number: 466-WE

Datasheet

Specifications

Design

Product brand

Clipsal

Product or component type

BC lamp holder adaptor

Colour tint

white electric

Sustainable offer status

Green Premium product

Physical

REACh Regulation

Reference contains Substances of Very High Concern above the threshold

EU RoHS Directive

Compliant

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure

ENVPEP1605009

Others

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Weight

16.0 g

Package 1 Height

40.0 mm

Package 1 width

22.0 mm

Package 1 Length

27.0 mm

Unit Type of Package 2

BB1

Number of Units in Package 2

10

Package 2 Weight

0.2 kg

Package 2 Height

7.0 cm

Package 2 width

9.2 cm

Package 2 Length

11.8 cm

Unit Type of Package 3

CAR

Number of Units in Package 3

200

Package 3 Weight

4.0 kg

Package 3 Height

25.0 cm

Package 3 width

21.4 cm

Package 3 Length

33.8 cm
Show all specifications

Frequently Asked Questions

hide show

What are the replacement spring charging motors for the Masterpact NT and NW?

Product Line:
Masterpact NT, Masterpact NW

Resolution:
Spring Charging Motor (MCH)
VoltageT-FrameW- & Y-Frame
FixedDrawoutFixedDrawout
AC
48S47391S47461S48207S48522
100–130S47395S47465S48211S48526
200–240S47396S47466S48212S48527
277S47398S47468S48213S48528
380–415S47398S47468S48214S48529
440–480S47400S47470S48215S48530
DC
24–30S47390S47460S48206S48521
48–60S47391S47461S48207S48522
100–130S47392S47462S48208S48523
200–250S47393S47463S48209S48524


See instruction bulletins,
Spring Charging Motor (MCH) for Masterpact® NT, Electrically-operated P-frame and NS630b–NS1600 Circuit Breakers
48049-236-01
Spring-charging Motor (MCH) for Masterpact® NW Circuit Breakers
48049-149-02

NW
NW Spring charging motor

NT
NT spring charging motor

What is the part number for the control card for the ATV312 drive?

Issue:
Control card for the ATV312 drive.

Product Line:
Altivar ATV312

Environment:
All

Cause:
N/A

Resolution:
VW3A31201 is the control  input/output control card only.  The package includes the control board which has the Input/Output screw terminal connections, RJ45 jack and a mounting screw. 

control IO card photo 1

What are possible causes of SCF1 motor short circuit faults on the ATV61 and ATV71?

Issue:
SCF1 faults on the ATV61 and ATV71.

Product Line:
ATV71 Altivar 71

Environment:
All

Cause:
SCF1 [Motor short circuit]     Short-circuit or grounding at drive output

Resolution:
  • Check the cables connecting the drive to the motor, and the motor’s insulation
    • Using a 1,000V Megger, test the motor and leads
    • Check for tight wiring connections
  • Perform tests via the [1.10 DIAGNOSTICS] menu.​
    • [Diagnostics] -> [Test Procedures] -> Thyristors Test and Transistor Test
  • ​Run the drive open circuit (with the motor disconnected, OPL turned off, and Motor Control Type set to V/F 2pts) and check the drive's output (T) terminals for balanced voltages phase to phase
    • ​[1.8 Fault Management] -> [Output Phase Loss] -> set to 'No' 
    • [1.4 Motor Control] -> [Motor control type] -> set to 'V/F 2pts'
  • Perform a diode check between U,W,V and PA+ PC-. Then measure between L1, L2, L3 and PA+ and PC-:
NOTE: This step should be performed when no line voltage is present on the drive. Power down the drive before performing this step. 
-Measure (using your meter's diode ABC scale) in one direction, then swap your leads and measure again
Measure between PA+ to L1,L2,L3 and between PC- to T1,T2,T3 (total of 6 measurements on the input and 6 measurements on the output)
-You should see 'OL' in one direction and a small voltage reading (approximately 0.3-.0.5V) in the other direction.
      
 

Video: How do I customize the display on the Altivar Process Drive?

Issue:
How do I adjust/customize the main display on the Altivar Process Drive?

Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)

Environment:
All serial numbers for Altivar Process Drive​

Resolution:



To adjust parameters on the top of the screen                               
- [My preferences] [Customization] [Param. Bar Select]   

A
To adjust parameters in the middle of the startup screen                               
[My preferences] [Customization] [Display Screen Type] [MPC]   
C
B
   

Will SoMove display the VW3A3408 resolver option cards serial number, part number or firmware version?

Issue:
Is SoMove showing option card serial number, part number or firmware version?

Product Line:
Altivar 71 only with the VW3A3408 resolver option card

Environment:
All

Cause:
Wants to know if SoMove will display the serial number, part number and firmware number.

Resolution:
SoMove will only display the reference part number of the card only see example below.

nh

 
 

What is the part number for the Modbus-to-Ethernet Gateway for the Altivar Drives and Altistart Soft Starters?

Issue:
Looking for the Modbus-to-Ethernet Gateway part number.

Product Line:
All

Environment:
All

Cause:
The drive or Soft Starter has built in Modbus communication. A gateway is needed in order to interface with Ethernet TCP/IP
 

Resolution:
The EGX100SD will allow interfacing between Modbus and Ethernet TCP/IP. The product Data Sheet is attached. 
 

PhotoB

Show More