C-Bus Schedule Plus Ver. 5 Software License Dongle, 2 Networks

C-Bus Schedule Plus Ver. 5 Software License Dongle, 2 Networks

C-Bus Schedule Plus Ver. 5 Software License Dongle, 2 Networks

Item Number: 5000SDSP2/5

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

C-Bus

Range

C-Bus

Product brand

Clipsal

Product or component type

software

Device application

  • control
  • scheduling
  • monitoring
    • Sustainable offer status

      Green Premium product

      Physical

      REACh Regulation

      Free of Substances of Very High Concern above the threshold

      EU RoHS Directive

      Compliant

      Mercury free

      Yes

      RoHS exemption information

      Yes

      China RoHS Regulation

      X

      Environmental Disclosure

      ENVPEP1701009EN

      Circularity Profile

      ENVEOLI1701009EN

      Others

      User language

      English

      Operating system

      Windows

      Unit Type of Package 1

      PCE

      Number of Units in Package 1

      1

      Package 1 Weight

      104 g

      Package 1 Height

      6 cm

      Package 1 width

      13.5 cm

      Package 1 Length

      15.9 cm

      Unit Type of Package 2

      CAR

      Number of Units in Package 2

      5

      Package 2 Weight

      0.82 kg

      Package 2 Height

      150 mm

      Package 2 width

      225 mm

      Package 2 Length

      350 mm
      Show all specifications

      Frequently Asked Questions

      hide show

      How to troubleshoot Schedule Plus hanging or crashing regularly?

      If Schedule Plus is hanging or crashing regularly even after a system reboot, please check the following

      1) Check the following files to ensure that PCI Polling has been disabled

      IMPORTANT: Please backup C-Gate Configuration and C-Bus Toolkit Database files prior to any changes in case of corruption. Also use Notepad to edit/save the recommended changes to avoid formatting issues. The path shown below is based on the default C-Gate installation paths. 

      Edit the following files using Notepad and use Ctrl + F to search for poll-interval - where found please change the parameter from default 60 to the disabled state 0 value. Note ProjectName relates to the site specific C-Bus Toolkit XML project
      C:\Clipsal\C-Gate2\config\C-GateConfig.txt
      C:\Clipsal\C-Gate2\tag\{ProjectName.XML}

      Upon changing and saving these 2 files a reboot of the C-Gate service and Schedule Plus program will be required or a system reboot to bring changes into effect. 

      2) Determine if the C-Bus Networks are being commissioned
      Discuss with your integrator or facilities manager if there are C-Bus Networks that are currently being worked on. 
      (see recommendation for 2 & 3 below)

      3) Determine if the C-Bus Networks are constantly going into a marginal state or an offline state, resyncing and coming back online
      Open the Schedule Plus C-Bus Network Manager via Projects | C-Bus Networks and check the Auto Refresh option and click the Refresh Button. If the same network is often becoming marginal or going offline it may be an indication of a hardware issue with a gateway device eg Network Interface or Network Bridge device or other C-Bus units on the network. 
      (see recommendation for 2 & 3 below)

      In the event C-Bus Networks are being commissioned or are exhibiting hardware issues it is recommended to temporarily not open and not use the network(s) in question if the issue is causing site to constantly hang or crash
      and re-enabled at a later date once the issues are resolved on site.

      Using the C-Bus Network Manager via Projects | C-Bus Network option 
      Select the network in question by double left clicking on it and then changing the 
      1) Use in Project to No and
      2) Open When Connecting to C-Bus to No
      and clicking OK to save changes
      Then restarting C-Gate service and Schedule Plus program or rebooting the machine to bring those changes into effect.

      How do we plug a C-BUS USB dongle on a server with out a USB port?

      This applies to a Headend PC that doesn’t have a USB port i.e a virtual machine that's running Homegate or Schedule Plus

      The solution is to use a Network-Attached USB Hub

      Please see link below for Network-Attached USB Hubs

      https://www.digi.com/products/usb-and-serial-connectivity/usb-over-ip-hubs/anywhereusb

      https://www.cnet.com/au/products/belkin-network-usb-hub/review/