Wiser for C-Bus Automation Controller

Wiser for C-Bus Automation Controller

Catalogue Number: 5500SHAC

Specifications

hide show
Package 1 Height
100 mm
Package 1 Length
160 mm
Package 1 width
115 mm
Range
Wiser
Product name
C-Bus Automation Controller
Product or component type
logic controller
Communication port protocol
  • C-Bus RJ45 (2000 devices)
  • IP (Internet Protocol) RJ45
  • serial link terminal block RS232
  • BACnet IP RJ45 (50 devices)
  • Modbus RTU terminal block RS485 (6 devices)
  • Modbus TCP RJ45
    • [Us] rated supply voltage
      24 V DC
      Power consumption in W
      2 W
      Local signalling
    • LED (green/red) for power
    • LED (green/red) for status indication
    • LED (green) for relay output (REL)
    • LED (multi-colour) for input status
    • LED (multi-colour) for RS232 link activity
    • LED (multi-colour) for serial link communication (RS485, RX, TX)
    • LED (green) for C-Bus status
    • LED (green/yellow) for Ethernet link
      • Port Ethernet
        10BASE-T/100BASE-TX
        Number of port
      • 1 USB 2.0 type A
      • 1 USB 1.1 type B
      • 1 RS232 (serial link)
      • 1 RS485 (Modbus)
      • 2 RJ45 (C-Bus)
      • 1 RJ45 (Ethernet)
        • Control type
        • smartphone or tablet
        • remote control
        • RESET push-button
        • local control
        • by touch panel
        • by web browser
        • RESET push-button cold restart
          • Web services
            web server
            Function available
          • visualisation
          • updateable software
            • Number of inputs
              1-1 dry contact
              Input impedance
            • 2.2 kOhm closed
            • 6.9 kOhm opened
              • Number of outputs
                1 relay changeover
                Output voltage
              • 24 V DC 1 A for relay
              • 48 V AC 1 A for relay
                • Connections - terminals
                • power supply: screw terminal 3 cable(s) 1.5-1.5 mm²
                • LED lamp: screw terminal 2 cable(s) 1.5-1.5 mm²
                • relay digital output: screw terminal 3 cable(s) 1.5-1.5 mm²
                • digital input: screw terminal 2 cable(s) 1.5-1.5 mm²
                • RS232 link: screw terminal 3 cable(s) 1.5-1.5 mm²
                • RS485 link: screw terminal 5 cable(s) 1.5-1.5 mm²
                  • Mounting support
                    DIN rail
                    Total number of 18 mm modules
                    6
                    Height
                    108 mm
                    Width
                    93 mm
                    Depth
                    63 mm
                    Market segment
                    residential
                    Ambient air temperature for operation
                    -5-45 °C
                    Operating altitude
                    <= 2000 m
                    Relative humidity
                    10-90 %
                    IP degree of protection
                    IP20
                    Directives
                  • 2011/65/EU - RoHS directive
                  • 1907/2006/EC - REACH directive
                  • 2002/96/EC - WEEE directive
                    • Standards
                    • EN 55022 class A
                    • AS/NZS CISPR 22
                      • Package 1 Weight
                        0.213 kg
                        Sustainable offer status
                        Green Premium product
                        REACh Regulation
                        Free of Substances of Very High Concern above the threshold
                        EU RoHS Directive
                        Compliant
                        Mercury free
                        Yes
                        RoHS exemption information
                        Yes
                        China RoHS Regulation
                        X
                        Environmental Disclosure
                        ENVPEP1701009EN
                        Circularity Profile
                        ENVEOLI1701009EN

                        Frequently Asked Questions

                        hide show

                        What is used as the C-Bus to Bacnet Gateway

                        The 5500NAC or 5500SHAC can be used as Bacnet gateway depending on the number of Bacnet points which are required.
                        The 5500NAC has 500 Bacnet Points and the 5500SHAC has 50 Bacnet points.
                        Bacnet is normally used by Building Management systems.

                        Does 5500SHAC Wiser for C-Bus Automation Controller come with a power supply?

                        5500SHAC does not come with a power supply. 
                        24Vdc, 10W Max, 2W typical plug-pack or similar needs to be purchased separately. 
                        For further information, please visit https://updates.clipsal.com/ClipsalOnline/Files/Brochures/W0001832.pdf

                         

                        Where to set Port numbers using NAC or SHAC

                        Access “Configuration” window on the web browser, select “System”, select “Services” which will allow you access to “HTTP server settings”, this is where your ports can be set.

                        How to import a background picture into the 5500SHAC

                        Issue: Importing a background image into the 5500SHAC is not a straightforward process.

                        Product Line:
                        C-Bus Automation controllers

                        Environment:
                        Internet Explorer, Mozilla Firefox, Google Chrome

                        Solution:
                        Will be filled in once I actually know the process myself

                        :CBUS: Can you operate the 5500shac network directly from the 5000EPT10W touchscreen?

                        Yes, using either crossover or straight through network cable

                        Touchsrcreen need to be on the same IP range as the Shac/Nac
                         

                         

                        How to control RS-232 enabled devices with C-Bus Network Automation Controller – 5500NAC (5500SHAC)?

                        A Configuration Guide exist on the Exchange Community, see the link below or the attachment.

                        How to control RS-232 enabled devices with C-Bus Network Automation Controller – 5500NAC



                         
                        Show More