C-Bus Passive Infrared Occupancy Detectors, 110 Degree, IP66

Catalogue Number: 5750WPL
c-bus ip66 infrascan learn
Colour Grey (GY)
  • Grey 1 PCE 1

Specifications

hide show
Range of product
  • Australian Series
  • C-Bus
    • Range
      C-Bus
      Product brand
      Clipsal
      Product or component type
      occupancy sensor
      Device application
      lighting
      Sensor type
      PIR
      Product specific application
      staircase monitoring
      [Ue] rated operational voltage
      15...36 V DC
      [In] rated current
      18 mA
      Communication network type
      C-Bus 100
      Number of channels
      1
      Type of setting
      light sensitivity adjustable
      Light intensity adjustment
      1-1 lux user selectable
      Data backed up
      non-volatile memory
      Local signalling
      LEDstatus:
      Resolution
      1 s
      Starting time
      5 s
      Horizontal detection angle
      0-110 °
      Time delay range
      0...1 s (switch-on)
      Duty cycle
      1090 min
      Detection face
    • lateral: 12 m
    • frontal: 18 m
      • Connections - terminals
        2 flying leads
        Material
        plastic
        Device mounting
        surface
        Mounting support
      • wall
      • ceiling
        • Mounting height
          2.4 m
          Fixing center
          84 mm
          Width
          74 mm
          Height
          111 mm
          Depth
          138 mm
          IP degree of protection
          IP66
          Ambient air temperature for operation
          0-45 °C
          Unit Type of Package 1
          PCE
          Number of Units in Package 1
          1
          Package 1 Weight
          340 g
          Package 1 Height
          12.6 cm
          Package 1 width
          17.6 cm
          Package 1 Length
          24.8 cm
          EU RoHS Directive
          Under investigation
          Circularity Profile
          ENVEOLI121002EN

          Frequently Asked Questions

          hide show

          What is the part code for a CBUS outdoor occupancy sensor

          The part code is 5750WPL

          Is the 750WPR Cbus compatible?

          No however the 5750WPL is the same sensor just cbus compatible

          Video: Program "Presence Detection" on C-Bus outdoor PIR sensor

          Video: Program "Presence Detection" on C-Bus outdoor PIR sensor

          Objective:
          Presence detection sets the sensor to trigger on motion. When motion is detected, the sensor sends a C-Bus command across C-Bus.
          this video will step through Program “Presence Detection”, it will cover those C-Bus sensors, 5751L, 5750WPL and 5753L with the old firmware v1.2.67.
          If having problem of programming Presence Detection please review FAQ “Program Presence Detection”

          Product Line:
          C-Bus Sensors: 5751L, 5750WPL and 5753L with the old firmware v1.2.67

          Environment:
          C-Bus Toolkit 1.15.5

          Resolution:
          • Open C-Bus Toolkit
          • Scan the Network
          • Double click the sensor to open its GUI
          • Select a control group from the “Key 4 Group” dropdown list, Presence Detection uses “Any Motion (AM)” function
          • Define the Expiry Time (5 minutes assigned by default) and click “OK”
          • Click “Apply” or “OK”
          • Save to Database and Physical Unit

          Top level --> Product category --> --> Building Automation and Control --> Building Management --> Building Management Systems --> C-Bus Automation system

          Video: Program "Absence Detection" on C-Bus outdoor PIR sensor

          Video: Program "Absence Detection" on C-Bus outdoor PIR sensor

          Objective:
          Absence detection sets the sensor to detect the absence of motion. If the lighting is on and the sensor detects the absence of motion, a timer is activated. When the timer expires and the sensor element still detects absence, a C-Bus command is sent to control lighting.
          This video will step through Program “Absence Detection”, it will cover those C-Bus sensors, 5751L, 5750WPL and 5753L with the old firmware v1.2.67.
          If having problem of programming Absence Dotation please review FAQ “Program Absence Detection”

          Product Line:
          C-Bus Sensors: 5751L, 5750WPL and 5753L with the old firmware v1.2.67

          Environment:
          C-Bus Toolkit 1.15.5

          Resolution:
          • Open C-Bus Toolkit
          • Scan the Network
          • Double click the sensor to open its GUI
          • Select a control group from the “Key 1 Group” dropdown list
          • Define the Expiry Time (5 minutes assigned by default) and click “OK”
          • Go to Key Functions tab and change the “On Key” on MD column for Short Press to “Idle”
          • A Confirm-21000 message will pop up
          • Click “YES” to accept the non-PIR functions
          • Click “Apply” or “OK”
          • Save to Database and Physical Unit
          Top level --> Product category --> --> Building Automation and Control --> Building Management --> Building Management Systems --> C-Bus Automation system

          Which outdoor sensors have a sensitivity adjustment

          The  part codes are  100SA360, 750WP and 750WPR

          Can 750WP be connected in parallel to control the same load .

          No. Need to use the 750WPR, three wire device when connecting in parallel
          For more information on the 750 series please visit the Clipsal web site on the link provided . https://www.clipsal.com/Trade/search-results?q=750w
          Show More