Specifications

hide show
Range of product
C-Bus
Range
C-Bus
Product brand
Clipsal
Product or component type
occupancy sensor
Device application
lighting
Product specific application
staircase monitoring
Sensor type
PIR
Protection type
creep zone protection
Type of setting
light sensitivity adjustable
Number of channels
1
Time delay range
0...1 s (switch-on)
Detection face
  • lateral: 7.5 m
  • frontal: 7.5 m
    • Movement detection area
      15 m
      Horizontal detection angle
      0-360 °
      Duty cycle
      1080 min
      Material
      plastic
      Device mounting
      flush
      Mounting height
      2.4 m
      REACh Regulation
      Free of Substances of Very High Concern above the threshold
      EU RoHS Directive
      Compliant
      Toxic heavy metal free
      Yes
      Mercury free
      Yes
      RoHS exemption information
      Yes
      China RoHS Regulation
       Pro-active China RoHS declaration (out of China RoHS legal scope)
      Circularity Profile
      ENVEOLI121002EN

      Documents & downloads

      hide show
      Filter items
      • All

      • CAD Files and Packs

      • Product Brochures

      • Installation Instruction

      • Product Environmental

      • End of Life Manual

      • Operating Manuals

      • System User Guide

      • Specifications

      • Software - Released

      Frequently Asked Questions

      hide show

      Does the Corridor Linking function available on C-Bus 5753L sensor?

      Yes, If the 5753L sensor has the latest firmware version V2.4.00.

      Can i get 5753L in black?

      No. Unfortunately, we do not.

      What is the cut out hole size for a CBUS motion detector 5753L

       The cut out hole size is 50mm

      Video: Program "Presence Detection" on C-Bus outdoor PIR sensor

      Video: Program "Presence Detection" on C-Bus outdoor PIR sensor

      Objective:
      Presence detection sets the sensor to trigger on motion. When motion is detected, the sensor sends a C-Bus command across C-Bus.
      this video will step through Program “Presence Detection”, it will cover those C-Bus sensors, 5751L, 5750WPL and 5753L with the old firmware v1.2.67.
      If having problem of programming Presence Detection please review FAQ “Program Presence Detection”

      Product Line:
      C-Bus Sensors: 5751L, 5750WPL and 5753L with the old firmware v1.2.67

      Environment:
      C-Bus Toolkit 1.15.5

      Resolution:
      • Open C-Bus Toolkit
      • Scan the Network
      • Double click the sensor to open its GUI
      • Select a control group from the “Key 4 Group” dropdown list, Presence Detection uses “Any Motion (AM)” function
      • Define the Expiry Time (5 minutes assigned by default) and click “OK”
      • Click “Apply” or “OK”
      • Save to Database and Physical Unit

      Top level --> Product category --> --> Building Automation and Control --> Building Management --> Building Management Systems --> C-Bus Automation system

      What is the main difference between part nos 5753L & 5753PEIRL

      The 5753PEIRL can control C-Bus by occupancy, light level and also via an IR remote, and can work in conjunction with a switch.

      The 5753L operates by occupancy, and can be programmed to operate with a switch.

      Video: Program "Absence Detection" on C-Bus outdoor PIR sensor

      Video: Program "Absence Detection" on C-Bus outdoor PIR sensor

      Objective:
      Absence detection sets the sensor to detect the absence of motion. If the lighting is on and the sensor detects the absence of motion, a timer is activated. When the timer expires and the sensor element still detects absence, a C-Bus command is sent to control lighting.
      This video will step through Program “Absence Detection”, it will cover those C-Bus sensors, 5751L, 5750WPL and 5753L with the old firmware v1.2.67.
      If having problem of programming Absence Dotation please review FAQ “Program Absence Detection”

      Product Line:
      C-Bus Sensors: 5751L, 5750WPL and 5753L with the old firmware v1.2.67

      Environment:
      C-Bus Toolkit 1.15.5

      Resolution:
      • Open C-Bus Toolkit
      • Scan the Network
      • Double click the sensor to open its GUI
      • Select a control group from the “Key 1 Group” dropdown list
      • Define the Expiry Time (5 minutes assigned by default) and click “OK”
      • Go to Key Functions tab and change the “On Key” on MD column for Short Press to “Idle”
      • A Confirm-21000 message will pop up
      • Click “YES” to accept the non-PIR functions
      • Click “Apply” or “OK”
      • Save to Database and Physical Unit
      Top level --> Product category --> --> Building Automation and Control --> Building Management --> Building Management Systems --> C-Bus Automation system
      Show More