C-Bus 360° Passive Infrared Occupancy Detector, Ceiling Mount

C-Bus 360° Passive Infrared Occupancy Detector, Ceiling Mount

C-Bus 360° Passive Infrared Occupancy Detector, Ceiling Mount

Item Number: 5753L

Datasheet

Specifications

Design

Sustainable offer status

Green Premium product

Range of product

C-Bus

Range

C-Bus

Product brand

Clipsal

Product or component type

occupancy sensor

Device application

lighting

Physical

Protection type

creep zone protection

Type of setting

light sensitivity adjustable

Number of channels

1

Movement detection area

15 m

Device mounting

flush

Mounting height

2.4 m

REACh Regulation

Free of Substances of Very High Concern above the threshold

REACh free of SVHC

Yes

EU RoHS Directive

Compliant

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure

ENVPEP121002EN

Circularity Profile

ENVEOLI121002EN

Sensor type

PIR

Material

Material

plastic

Others

Time delay range

0...1 s (switch-on)

Detection face

  • lateral: 7.5 m
  • frontal: 7.5 m

Horizontal detection angle

0...360 °

Duty cycle

1080 min

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Weight

200.0 g

Package 1 Height

9.529 cm

Package 1 width

12.706 cm

Package 1 Length

16.538 cm

Unit Type of Package 2

CAR

Number of Units in Package 2

10

Package 2 Weight

2420.0 g

Package 2 Height

30 cm

Package 2 width

43.2 cm

Package 2 Length

22 cm

Unit Type of Package 3

P12

Number of Units in Package 3

160

Package 3 Weight

47720.0 g

Package 3 Height

95 cm

Package 3 width

80 cm

Package 3 Length

120 cm

WEEE

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

Product specific application

staircase monitoring
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • Product Brochures

  • CAD Files and Packs

  • Technical Leaflet

  • Installation Instruction

  • End of Life Manual

  • Product Environmental

  • Operating Manuals

  • Specifications

  • Application Solutions

  • Declaration of Conformity

  • Certificates (MSDS)

  • Software - Archive

  • Software - Release

Frequently Asked Questions

hide show

How to Program "Absence Detection" on C-Bus outdoor PIR sensor?

Objective:
Absence detection sets the sensor to detect the absence of motion. If the lighting is on and the sensor detects the absence of motion, a timer is activated. When the timer expires and the sensor element still detects absence, a C-Bus command is sent to control lighting.
This article will guide you how to program “Absence Detection”, it will cover those C-Bus sensors, 5751L, 5750WPL and 5753L with the old firmware v1.2.67.

Product Line:
C-Bus Sensors: 5751L, 5750WPL and 5753L with the old firmware v1.2.67

Environment:
C-Bus Toolkit 1.15.5

Resolution:
  1. Open C-Bus Toolkit
  2. Scan the Network
  3. Double click the sensor to open its GUI
  4. Select a control group from the “Key 1 Group” dropdown list
  5. Define the Expiry Time (5 minutes assigned by default) and click “OK”
  6. Go to Key Functions tab and change the “On Key” on MD column for Short Press to “Idle”
  7. A Confirm-21000 message will pop up
  8. Click “YES” to accept the non-PIR functions
  9. Click “Apply” or “OK”
  10. Save to Database and Physical Unit

What is the cut out hole size for a CBUS motion detector 5753L

 The cutout hole size is 50mm

What is the surface mount equivalent to the 5753L?

The part code is 5754ODPE.