OCC- LL SENSOR SURFACE MNT 360

OCCUPANCY, LIGHT LEVEL SENSOR SURFACE MOUNT 360 DEGREE

Catalogue Number: 5754ODPE
OCC- LL SENSOR SURFACE MNT 360
Colour:
Colour: Per UOM Std.
  • 1 PCE 1

Specifications

hide show
Range of product
C-Bus
Range
C-Bus
Product brand
Clipsal
Product or component type
occupancy and light level sensor
Device application
lighting
Product specific application
staircase monitoring
Sensor type
PIR
Protection type
creep zone protection
Type of setting
light sensitivity adjustable
Number of channels
1
Time delay range
0...1 s (switch-on)
Detection face
  • lateral: 4.85 m
  • frontal: 4.85 m
    • Movement detection area
      9.7 m
      Horizontal detection angle
      0-360 °
      Duty cycle
      1080 min
      Material
      plastic
      Device mounting
      surface
      Mounting height
      2.7 m
      REACh Regulation
      Free of Substances of Very High Concern above the threshold
      EU RoHS Directive
      Compliant
      Toxic heavy metal free
      Yes
      Mercury free
      Yes
      RoHS exemption information
      Yes
      China RoHS Regulation
       Pro-active China RoHS declaration (out of China RoHS legal scope)
      Circularity Profile
      ENVEOLI121002EN

      Documents & downloads

      hide show
      Filter items
      • All

      • CAD Files and Packs

      • Product Brochures

      • Installation Instruction

      • Product Environmental

      • End of Life Manual

      • Operating Manuals

      • System User Guide

      • Specifications

      • Software - Released

      Frequently Asked Questions

      hide show

      Video: Program “Absence Detection” using Classic Configuration

      Objective:
      Absence detection sets the sensor to detect the absence of motion. If the lighting is on and the sensor detects the absence of motion, a timer is activated. When the timer expires and the sensor element still detects absence, a C-Bus command is sent to control lighting.
      This video will step through Program “Absence Detection” using Classic Configuration, it this will cover those C-Bus sensors, 5753L, 5753PEIRL, 5754ODPE, 5754ODPEIR.
      Product Line:
      C-Bus Sensors: 5753L, 5753PEIRL, 5754ODPE, 5754ODPEIR
      Environment:
      C-Bus Toolkit 1.15.2
      Resolution:
      Right click on the sensor and select “Open Unit in Classic” to open its GUI in Classic
      Select a group from the “Virtual Key 1 Group” dropdown list
      Click the  button to define the Expiry Time (5 minutes assigned by default) and click “OK”
      Go to Key Functions tab and change the Short Press “On Key” on Key 2 column to “Idle”
      A Confirm-12413 message will pop up
      Click “NO” to keep the Occupancy events for this sensor
      Click “Apply” or “OK”