Why does my smoke detector 755SMA keep false alarming?

Smoke detectors are very sensitive to insects and dust particals. In the event of false alarming you may need to clean your alarm. The alarm can be vacuumed or brushed with a soft brush to remove dust, dirt or kitchen grease that has accumulated. Apply a small amount of insect surface spray to a cloth and wipe around alarm/s every 3-6 months to mitigate insect ingress. It is recommended that the smoke alarm is inspected monthly to ensure it is free from dirt, dust and insects. If this doesn't resolve the false alarming you may be requied to have it serviced and/ or replaced if necessary.

ALWAYS TEST THE SMOKE ALARM AFTER CLEANING 

For further information please visit https://www.clipsal.com/safety?tab-player-1=0

Can 755PSMA, 755SMA , 755PSMA2 and 755PSMA4 be interlinked together?

Yes they can all be interlinked together.
Interconnecting smoke alarms is a method of joining a series of alarms so that if any one alarm senses smoke, all the connected alarms will operate (alarm). 
A 9 V signal is applied to the interconnect wire (referenced to neutral) to alarm all the other interconnected alarms.
• All interconnected smoke alarms must be supplied from the same circuit.
• A common Neutral must be used for the Interconnect to operate.
• DO NOT connect the Interconnect wire to Active or Neutral.
• A maximum of 40 Clipsal 755 smoke alarms can be installed on one circuit (wired interconnection only).
• Only Clipsal smoke alarms can be interconnected with each other.
Failure to follow these instructions may result in injury and equipment damage / malfunction.