Acti9 iDPN N VigiArc 1PN C 6A...25A 30mA A
Acti9 iDPN VigiARC - System Image - Closed - New Zealand
Acti9 iDPN N VigiArc 1PN C 6A...25A 30mA A
Acti9 iDPN VigiARC - System Image - Closed - New Zealand

iDPN N VigiARC C 16A 6000A 30mA Type A 16A

Catalogue Number: A9T26616

Specifications

hide show
Range
Acti9
Product name
Acti9 iDPN N VigiARC
Product or component type
arc fault detection RCBO
Product specific application
arc fault detection
Standards
  • EN/IEC 62606
  • AS/NZS 61009.1
    • Device short name
      iDPN N VigiARC
      Poles description
      1P + N
      [In] rated current
      16 A
      Number of protected poles
      1
      Curve code
      C
      Breaking capacity
      6000 A at 240 V AC 50 Hz conforming to AS/NZS 61009.1
      Rated breaking and making capacity
      Idm 500 A at 240 V AC 50 Hz conforming to AS/NZS 61009.1
      Neutral position
      left
      Earth-leakage sensitivity
      30 mA
      Network type
      AC
      Earth-leakage protection time delay
      instantaneous
      Earth-leakage protection class
      class A
      Suitability for isolation
      yes
      Residual current tripping technology
      voltage dependent
      Trip unit technology
      thermal-magnetic
      Earth-leakage protection
      integrated
      Network frequency
      50 Hz
      [Ue] rated operational voltage
    • 230/240 V AC 50 Hz conforming to AS/NZS 61009.1
    • 230/240 V AC 50 Hz conforming to IEC 62606
      • Device location in system
        outgoer
        Magnetic tripping limit
        5...10 x In
        Limitation class
        3 conforming to AS/NZS 61009.1
        [Ui] rated insulation voltage
      • 250 V AC 50 Hz between phase and neutral
      • 400 V AC 50 Hz between phases
        • Threshold tripping voltage
          275 V +/- 5 V
          [Uimp] rated impulse withstand voltage
          4 kV conforming to AS/NZS 61009.1
          Contact position indicator
          yes
          Control type
          toggle
          Local signalling
          ON, OFF, fault trip
          Mounting mode
          clip-on
          Mounting support
          DIN rail
          Mechanical durability
          20000 cycles
          Electrical durability
          20000 cycles 240 V AC 50 Hz conforming to AS/NZS 61009.1
          Overvoltage category
          III
          Locking options description
          padlocking device
          Cable entry
          top and bottom
          Connections - terminals
        • tunnel type terminal for 2 cable(s) 2.5-2.5 mm² rigid
        • tunnel type terminal for 1 cable(s) 16-16 mm² rigid
        • tunnel type terminal for 2 cable(s) 2.5-2.5 mm² flexible
        • tunnel type terminal for 1 cable(s) 10-10 mm² flexible
          • Wire stripping length
            14 mm
            Tightening torque
            2-2 N.m
            Comb busbar and distribution block compatibility
            YES
            9 mm pitches
            4
            Height
            91 mm
            Width
            36 mm
            Depth
            75 mm
            Net weight
            205 g
            Heat dissipation
            3.50-3.50 W at 240 V - 16 A
            IP degree of protection
            IP20 conforming to IEC 60529
            Pollution degree
          • 2 conforming to AS/NZS 61009.1
          • 2 conforming to IEC 62606
            • Tropicalisation
              severity B conforming to IEC 60068-2-30 for 28 d
              Relative humidity
              95-95 % at 55-55 °C
              Operating altitude
              2000 m
              Ambient air temperature for operation
              -25-60 °C
              Ambient air temperature for storage
              -40-80 °C
              Quality labels
              RCM
              Sustainable offer status
              Green Premium product
              REACh Regulation
              Free of Substances of Very High Concern above the threshold
              EU RoHS Directive
              Compliant
              Mercury free
              Yes
              RoHS exemption information
              Yes
              China RoHS Regulation
              Product out of China RoHS scope. Substance declaration for your information
              Environmental Disclosure
              ENVPEP1906001EN
              Circularity Profile
              ENVEOLI1906001EN
              Warranty
              24 months

              Documents & downloads

              hide show
              Filter items
              • All

              • Product Environmental

              • Installation Instruction

              • End of Life Manual

              • Certificates (MSDS)

              Frequently Asked Questions

              hide show

              Does A9A26976 go with iDPN N VIGI?

              No. Unfortunately it does not and we don't do the terminal Shiels for iDPN N vigi as the screws are small.

              What is the difference between A9D32620 and A9D33620 RCBO Acti 9 devices?

               
               

              A9D33620 = SI (Super Immunised)
              A9D32620 = Type A (AC or pulsating DC)

              Type A RCBO = Tripping is ensured for residual sinusoidal alternating currents and residual pulsating direct currents, whether suddenly applied or slowly rising.
              Type Si RCBO = With all the features of a Type A device, “Si” type Super Immunised earth leakage protection range has been specially developed to be used with loads or in environments causing disturbances. Examples are lightning or switching surges, harmonics generated by increasing number of loads and constant load leakage current from electronic ballasts, speed drives, computers, etc. The Si increases safety and allows improved continuity of supply.
               

              What is the bulletin number for the startup and receiving manual for the Altivar ATV66 drive?

              Issue:
              Looking for the bulletin number for the startup and receiving manual for the Altivar ATV66 drive?

              Product Line:
              Altivar Machines, Altivar 66

              Environment:
              All models

              Cause:
              N/A

              Resolution:
              The bulletin number is VD0C06S304 "Constant and Variable Torque: 1 to 400 hp, 460 V and 1 to 50 hp, 230 V Receiving, Installation and Start-Up".Start-Up Bulletin: https://www.schneider-electric.us/en/download/document/VD0C06S304/Repair Parts Addendum: https://www.schneider-electric.us/en/download/document/30072-450-73/
               

              Is there a shunt trip that can be used in conjunction with a iSW series?

              No unfortunately the ISW series can't be used with shunt release.

              For further information please visit Global Specialist in Energy Management | Schneider Electric