Acti9 iDPN N VigiArc 1PN C 6A...25A 30mA A

iDPN N VigiARC C 25A 6000A 30mA Type A 25A

Catalogue Number: A9T26625

Specifications

hide show
Range
Acti9
Product name
Acti9 iDPN N VigiARC
Product or component type
arc fault detection RCBO
Product specific application
arc fault detection
Standards
  • EN/IEC 62606
  • AS/NZS 61009.1
    • Device short name
      iDPN N VigiARC
      Poles description
      1P + N
      Number of protected poles
      1
      Curve code
      C
      Breaking capacity
      6000 A at 240 V AC 50 Hz conforming to AS/NZS 61009.1
      Rated breaking and making capacity
      Idm 500 A at 240 V AC 50 Hz conforming to AS/NZS 61009.1
      Neutral position
      left
      Network type
      AC
      Earth-leakage protection time delay
      instantaneous
      Earth-leakage protection class
      class A
      Suitability for isolation
      yes
      Residual current tripping technology
      voltage dependent
      Trip unit technology
      thermal-magnetic
      Earth-leakage protection
      integrated
      Network frequency
      50 Hz
      [Ue] rated operational voltage
    • 230/240 V AC 50 Hz conforming to AS/NZS 61009.1
    • 230/240 V AC 50 Hz conforming to IEC 62606
      • Device location in system
        outgoer
        Magnetic tripping limit
        5...10 x In
        Limitation class
        3 conforming to AS/NZS 61009.1
        [Ui] rated insulation voltage
      • 250 V AC 50 Hz between phase and neutral
      • 400 V AC 50 Hz between phases
        • Threshold tripping voltage
          275 V +/- 5 V
          [Uimp] rated impulse withstand voltage
          4 kV conforming to AS/NZS 61009.1
          Contact position indicator
          yes
          Control type
          toggle
          Local signalling
          ON, OFF, fault trip
          Mounting mode
          clip-on
          Mounting support
          DIN rail
          Mechanical durability
          20000 cycles
          Electrical durability
          10000 cycles 240 V AC 50 Hz conforming to AS/NZS 61009.1
          Overvoltage category
          III
          Locking options description
          padlocking device
          Cable entry
          top and bottom
          Connections - terminals
        • tunnel type terminal for 2 cable(s) 2.5-2.5 mm² rigid
        • tunnel type terminal for 1 cable(s) 16-16 mm² rigid
        • tunnel type terminal for 2 cable(s) 2.5-2.5 mm² flexible
        • tunnel type terminal for 1 cable(s) 10-10 mm² flexible
          • Wire stripping length
            14 mm
            Tightening torque
            2-2 N.m
            Comb busbar and distribution block compatibility
            YES
            9 mm pitches
            4
            Height
            91 mm
            Width
            36 mm
            Depth
            75 mm
            Net weight
            205 g
            Heat dissipation
            6.50-6.50 W at 240 V - 25 A
            IP degree of protection
            IP20 conforming to IEC 60529
            Pollution degree
          • 2 conforming to AS/NZS 61009.1
          • 2 conforming to IEC 62606
            • Tropicalisation
              severity B conforming to IEC 60068-2-30 for 28 d
              Relative humidity
              95-95 % at 55-55 °C
              Operating altitude
              2000 m
              Ambient air temperature for operation
              -25-60 °C
              Ambient air temperature for storage
              -40-80 °C
              Quality labels
              RCM
              Sustainable offer status
              Green Premium product
              REACh Regulation
              Free of Substances of Very High Concern above the threshold
              EU RoHS Directive
              Compliant
              Mercury free
              Yes
              RoHS exemption information
              Yes
              China RoHS Regulation
              Product out of China RoHS scope. Substance declaration for your information
              Environmental Disclosure
              ENVPEP1906001EN
              Circularity Profile
              ENVEOLI1906001EN
              Halogen content performance
              Halogen free plastic parts product
              Warranty
              24 months

              Documents & downloads

              hide show
              Filter items
              • All

              • Installation Instruction

              • Product Environmental

              • End of Life Manual

              • Certificates (MSDS)

              Frequently Asked Questions

              hide show

              will the A9A26929 fit on a C60-DC MCB?

              No, those are designed to fit onto the acti9 AC MCBs for those MCBs use the A9N26929

              Are the A9N18359 and A9A26924 compatible?

              The ref A9N18359 is C120 MCB (Multi9 design in the white material).

              The ref A9A26924 is iOF auxiliary (Aciti9 design for iC60 MCB).

              I can confirm that the parts A9N18359 and A9A26924 are not compliant with each other

               

              What are the codes for the Fault Arc Detection Devices?

              The part numbers for the Fault Arc Detection Devices are as follows.
              6A - A9FDB606
              10A - A9FDB610
              16A - A9FDB616
              20A - A9FDB620
              25A - A9FDB625

              What is the difference between A9D32620 and A9D33620 RCBO Acti 9 devices?

               
               

              A9D33620 = SI (Super Immunised)
              A9D32620 = Type A (AC or pulsating DC)

              Type A RCBO = Tripping is ensured for residual sinusoidal alternating currents and residual pulsating direct currents, whether suddenly applied or slowly rising.
              Type Si RCBO = With all the features of a Type A device, “Si” type Super Immunised earth leakage protection range has been specially developed to be used with loads or in environments causing disturbances. Examples are lightning or switching surges, harmonics generated by increasing number of loads and constant load leakage current from electronic ballasts, speed drives, computers, etc. The Si increases safety and allows improved continuity of supply.
               

              What are the codes of the items supplied with the 3 phase EV parking protection kits?

              Parts that should be supplied as follows:

              KITPARKING22-1:
              A9F54440 x 1, MCB, iC60H 4P 40A C Curve
              A9Z51440 x 1, RCD, iIDP 4P 40A 30mA Type B, 400V
              A9A26969 x 2, Under voltage release, iMNX 220 240VAC
              A9F44204 x 1, MCB, iC60N 2P 4A C Curve
              A9R91240 x 1, RCCB, iID 2P 40A 30mA Type Asi
              A9A26924 x 2, Aux contact, iOF 240 415VAC 24 130VDC

              KITPARKING22-2:
              A9F54440 x 2, MCB, iC60H 4P 40A C Curve
              A9Z51440 x 2, RCD, iIDP 4P 40A 30mA Type B, 400V
              A9A26969 x 3, Under voltage release, iMNX 220 240VAC
              A9F44204 x 1, MCB, iC60N 2P 4A C Curve
              A9R91240 x 1, RCCB, iID 2P 40A 30mA Type Asi
              A9A26924 x 4, Aux contact, iOF 240 415VAC 24 130VDC
               

              What is the bulletin number for the startup and receiving manual for the Altivar ATV66 drive?

              Issue:
              Looking for the bulletin number for the startup and receiving manual for the Altivar ATV66 drive?

              Product Line:
              Altivar Machines, Altivar 66

              Environment:
              All models

              Cause:
              N/A

              Resolution:
              The bulletin number is VD0C06S304 "Constant and Variable Torque: 1 to 400 hp, 460 V and 1 to 50 hp, 230 V Receiving, Installation and Start-Up".Start-Up Bulletin: https://www.schneider-electric.us/en/download/document/VD0C06S304/Repair Parts Addendum: https://www.schneider-electric.us/en/download/document/30072-450-73/
               