Acti9 iID - Residual Current Circuit Breaker - 4P - 63A - 30mA - B EV type
Acti9 iID 4P 63A 30mA B type EV 400V Residual Current Circuit Breaker
Acti9 iID - Residual Current Circuit Breaker - 4P - 63A - 30mA - B EV type
Acti9 iID 4P 63A 30mA B type EV 400V Residual Current Circuit Breaker

Residual Current Circuit Breaker, 4P, 63A, 30mA, B EV Type

Catalogue Number: A9Z51463

Specifications

hide show
Range
Acti9
Product name
Acti9 iID
Product or component type
residual current circuit breaker (RCCB)
Device short name
iID
Device application
Electrical Vehicle charger
Poles description
4P
Neutral position
left
[In] rated current
63 A
Network type
AC
Earth-leakage sensitivity
30 mA
Earth-leakage protection time delay
instantaneous
Earth-leakage protection class
type B-EV (Electric Vehicle)
Quality labels
  • VDE
  • NF
  • IMQ
  • KEMA
    • Device location in system
    • outgoer
    • group incomer
      • Network frequency
        50 Hz
        [Ue] rated operational voltage
        400 V AC 50 Hz
        Rated breaking and making capacity
      • Idm 1500 A
      • Im 1500 A
        • Rated conditional short-circuit current
          10 kA
          [Ui] rated insulation voltage
          500 V
          [Uimp] rated impulse withstand voltage
          6 kV
          Contact position indicator
          yes
          Control type
          toggle
          Local signalling
        • ON/OFF indication
        • trip indicator
          • Mounting mode
            clip-on
            Mounting support
            DIN rail
            Comb busbar and distribution block compatibility
            top or bottom: tooth
            Connection pitch
            9 mm pitches
            8
            Height
            88 mm
            Width
            72 mm
            Depth
            79 mm
            Net weight
            415 g
            Mechanical durability
            20000 cycles
            Electrical durability
            15000 cycles
            Locking options description
            padlocking device
            Connections - terminals
          • double terminal front 1-35 mm² rigid
          • double terminal front 1-25 mm² flexible
          • double terminal front 1-25 mm² flexible with ferrule
          • double terminal back 1-25 mm² rigid
          • double terminal back 1-16 mm² flexible
          • double terminal back 1-16 mm² flexible with ferrule
            • Wire stripping length
              14 mm for top or bottom connection
              Tightening torque
              3.5-3.5 N.m top or bottom
              Standards
            • IEC 61008-2-1
            • IEC/EN 62423
            • EN 61008-2-1
              • Product certifications
              • CCC
              • KC
                • IP degree of protection
                • IP20 conforming to IEC 60529
                • IP40 (modular enclosure) conforming to IEC 60529
                  • IK degree of protection
                    IK05
                    Pollution degree
                    3
                    Overvoltage category
                    IV
                    Electromagnetic compatibility
                    8/20 µs impulse withstand, 3 kA conforming to EN/IEC 61008-1
                    Operating altitude
                    0...2000 m
                    Ambient air temperature for operation
                    -25-60 °C
                    Ambient air temperature for storage
                    -40-85 °C
                    Unit Type of Package 1
                    PCE
                    Number of Units in Package 1
                    1
                    Package 1 Weight
                    450 g
                    Package 1 Height
                    7.5 cm
                    Package 1 width
                    8.5 cm
                    Package 1 Length
                    10 cm
                    Unit Type of Package 2
                    S03
                    Number of Units in Package 2
                    27
                    Package 2 Weight
                    12.565 kg
                    Package 2 Height
                    30 cm
                    Package 2 width
                    30 cm
                    Package 2 Length
                    40 cm
                    Sustainable offer status
                    Green Premium product
                    REACh Regulation
                    Free of Substances of Very High Concern above the threshold
                    EU RoHS Directive
                    Compliant
                    Mercury free
                    Yes
                    RoHS exemption information
                    Yes
                    China RoHS Regulation
                    Product out of China RoHS scope. Substance declaration for your information
                    Environmental Disclosure
                    ENVPEP1811009EN
                    Circularity Profile
                    ENVEOLI1811009EN
                    WEEE
                    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

                    Documents & downloads

                    hide show
                    Filter items
                    • All

                    • CAD Files and Packs

                    • Product Brochures

                    • Catalog Page

                    • Technical Data Catalogues

                    • End of Life Manual

                    • Product Environmental

                    • Installation Instruction

                    • Operating Manuals

                    • Application Solutions

                    • Certificates (MSDS)

                    • Declaration of Conformity

                    Frequently Asked Questions

                    hide show

                    What is the replacement for the 16756?

                    Replacement RCCD is A9Z61463

                    What is the suitable vigi unit to suit with the A9F54332?

                    A9F54332 is a 3 pole breaker.
                    They have an option of having 3 pole vigi (A9V51363) or 4 pole vigi (A9V02763) for neutral conection .

                    What are the codes of the items supplied with the 3 phase EV parking protection kits?

                    Parts that should be supplied as follows:

                    KITPARKING22-1:
                    A9F54440 x 1, MCB, iC60H 4P 40A C Curve
                    A9Z51440 x 1, RCD, iIDP 4P 40A 30mA Type B, 400V
                    A9A26969 x 2, Under voltage release, iMNX 220 240VAC
                    A9F44204 x 1, MCB, iC60N 2P 4A C Curve
                    A9R91240 x 1, RCCB, iID 2P 40A 30mA Type Asi
                    A9A26924 x 2, Aux contact, iOF 240 415VAC 24 130VDC

                    KITPARKING22-2:
                    A9F54440 x 2, MCB, iC60H 4P 40A C Curve
                    A9Z51440 x 2, RCD, iIDP 4P 40A 30mA Type B, 400V
                    A9A26969 x 3, Under voltage release, iMNX 220 240VAC
                    A9F44204 x 1, MCB, iC60N 2P 4A C Curve
                    A9R91240 x 1, RCCB, iID 2P 40A 30mA Type Asi
                    A9A26924 x 4, Aux contact, iOF 240 415VAC 24 130VDC
                     

                    What is the Australian equivalent for the A9R41263

                    For a Type A RCCB, the following part name will be suitable: A9R51263
                    For a Type AC RCCB, the following part name will be suitable: A9R41263

                    Old Merlin Gerin Code 23382 4p 40amp 30ma RCCB is now ?

                    Code now is A9R51440