AD63 K C 6A…32A 1PN 30mA 6000A A RCCB with overcurrent protection (RCBO)

AD63 K - earth leakage circuit breaker - 1P+N - C - 10A - 30mA - 6000A - A-TYPE

Catalogue Number: DOM12530
AD63 K C 6A…32A 1PN 30mA 6000A A RCCB with overcurrent protection (RCBO)
Colour:
Colour: Per UOM Std.
  • 1 PCE 1

Specifications

hide show
Device application
distribution
Range
Domae
Range of product
Domae
Product name
AD63 K
Product or component type
residual current breaker with overcurrent protection (RCBO)
Poles description
1P + N
Neutral position
left
Earth-leakage protection class
type A
Suitability for isolation
yes
[In] rated current
10 A at 30 °C
Network type
AC
Network frequency
50 Hz
[Ue] rated operational voltage
230/240 V AC 50 Hz
Trip unit technology
thermal-magnetic
Curve code
C
Magnetic tripping limit
5...10 x In
Earth-leakage sensitivity
30 mA
Earth-leakage protection time delay
instantaneous
Breaking capacity
6000 A Icn at 230/240 V AC 50 Hz
Electrical insulation class
class II
Limitation class
3
[Ui] rated insulation voltage
400 V AC 50 Hz
Contact position indicator
yes
Control type
toggle
Local signalling
ON/OFF indication
Mounting support
DIN rail
Comb busbar and distribution block compatibility
YES
9 mm pitches
2
Height
93 mm
Width
18 mm
Depth
70 mm
Net weight
136 g
Mechanical durability
20000 cycles
Provision for padlocking
padlockable
Locking options description
by padlocks
Connections - terminals
  • screw clamp terminal (upstream) 1-16 mm² rigid
  • screw clamp terminal (upstream) 1-16 mm² flexible
  • screw clamp terminal (downstream) 1-10 mm² rigid
  • screw clamp terminal (downstream) 1-10 mm² flexible
    • Wire stripping length
    • 14 mm for upstream connection
    • 11 mm for downstream connection
      • Tightening torque
      • 2-2 N.m upstream
      • 2-2 N.m downstream
        • Earth-leakage protection
          integrated
          Standards
        • IEC 61009-1
        • AS/NZS 61009
          • Ambient air temperature for operation
            -25-55 °C
            Ambient air temperature for storage
            -30-70 °C
            Sustainable offer status
            Green Premium product
            REACh Regulation
            Free of Substances of Very High Concern above the threshold
            REACh free of SVHC
            Yes
            EU RoHS Directive
            Compliant
            Mercury free
            Yes
            RoHS exemption information
            Yes
            China RoHS Regulation
            Product out of China RoHS scope. Substance declaration for your information
            Environmental Disclosure
            ENVPEP100702EN_V1
            Circularity Profile
            N/A

            Documents & downloads

            hide show
            Filter items
            • All

            • CAD Files and Packs

            • Technical Data Catalogues

            • Installation Instruction

            Frequently Asked Questions

            hide show

            Can the Domae Earth leakage RCBO DOM12530 be Top or Bottom Fed?

            Yes, the feed can be supplied to the top or bottom of the Domae RCBO's.

            How is it possible to determine if an Enercept Meter is the Basic or Enhanced model?

            A System ID register located at addresses 30 (Integer) and 315 (Float) exists within the Enercept Meter. Reading that register will yield one of two values:
            A value of 15022 will be returned from the Enhanced Enercept model.
            A value of 15023 will be returned from the Basic Enercept model.