Browse all
Browse all

Resi9 Surge arrester 1P, 40kA, with local signalling

Resi9 Surge arrester 1P, 40kA, with local signalling

Item Number: R9L40102

Datasheet

Product Dimensions

Width icon

Width18 mm

Height icon

Height85 mm

Depth icon

Depth64 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range Resi9
Product or component type cartridge
Device application distribution
Product destination surge protection device 1P

Physical

Standards
  • IEC 61643-11:2011
  • EN 61643-11:2012
[ue] rated operational voltage 240 V +/- 6 % AC 50/60 Hz
Local signalling flag (white/red)
Mounting mode plug-in
Mounting support into SPD module
Height 85 mm
Width 18 mm
Depth 64 mm
Net weight 51 g
Ip degree of protection IP20
Ik degree of protection IK03 conforming to IEC 62262
Relative humidity 5...95 % at 55 °C
Ambient air temperature for operation -25...70 °C
Ambient air temperature for storage -40...85 °C
Mercury free Yes
Rohs exemption information Yes
Reach regulation Reference contains Substances of Very High Concern above the threshold
China rohs regulation Product out of China RoHS scope
Eu rohs directive Compliant By Exemption
California proposition 65 WARNING: This product can expose you to chemicals including: Lead, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
California proposition 65 WARNING: This product can expose you to chemicals including: Lead, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Others

Life cycle assessment data Yes
Legacy weee scope In
Package 1 bare product quantity 1
Package 2 bare product quantity 84
Package 3 bare product quantity 1008
Average percentage of recycled plastic content 0 %
Outside of Europe
Weee label N/A
Weee applicability Finished product
Warranty duration(in months) bmecat 18
Poles description 1P
Surge arrester type electrical distribution network
Quality labels RCM
Surge arrester class type type 2
Surge arrester technology MOV
Earthing system
  • TN-C
  • TN-S
  • TT
Nominal discharge current 15 kA conforming to IEC 61643-11
Maximum discharge current 40 kA conforming to IEC 61643-11
[uc] maximum continuous operating voltage 350 V AC
Maximum [up] voltage protection level <1.6 kV type 2
[ures] residual voltage 1545 V
9 mm pitches 2
Targeted country New Zealand
Pollution degree 2
Operating altitude 0...2000 m
Unit type of package 1 PCE
Number of units in package 1 1
Package 1 height 8.4 cm
Package 1 width 2 cm
Package 1 length 9.8 cm
Package 1 weight 95 g
Unit type of package 2 CAR
Number of units in package 2 84
Package 2 height 20 cm
Package 2 width 29.9 cm
Package 2 length 39.8 cm
Package 2 weight 7.4 kg
Unit type of package 3 P06
Number of units in package 3 1008
Package 3 height 75 cm
Package 3 width 60 cm
Package 3 length 80 cm
Package 3 weight 94.8 kg
Total lifecycle carbon footprint 2 kg CO2 eq.
Carbon footprint of the manufacturing phase [a1 to a3] 0.5288850340136055
Carbon footprint of the manufacturing phase [a1 to a3] 0.5 kg CO2 eq.
Carbon footprint of the distribution phase [a4] 0.011498231292517007
Carbon footprint of the distribution phase [a4] 0 kg CO2 eq.
Carbon footprint of the installation phase [a5] 0.04115180272108844
Carbon footprint of the installation phase [a5] 0 kg CO2 eq.
Carbon footprint of the use phase [b2, b3, b4, b6] 1.6604399585921326
Carbon footprint of the use phase [b2, b3, b4, b6] 2 kg CO2 eq.
Sustainable packaging No
Carbon footprint of the end-of-life phase [c1 to c4] 0.17772108843537418
Carbon footprint of the end-of-life phase [c1 to c4] 0.2 kg CO2 eq.
Energy efficiency optimized False
Take-back No
Product contributes to saved and avoided emissions No
Removable battery N/A
Total lifecycle carbon footprint 2.419696115054718
Average percentage of recycled metal content 0 %
Packaging made with recycled cardboard No
Packaging without single use plastic No
End of life manual availability N/A
Take-back No
Warranty (in months) 18

Frequently Asked Questions

Does the Resi9 SPD require an additional protection device (MCB)?

Hide Show
We recommend using Resi9 MCB backup protection device for Resi9 SPD, 1P 40A MCB (R9F06140) for 1P SPD (R9L40100).


Why a back up protection is necessary?
(1) Protect upstream fuse/breaker - cascading 
(2) Ensure the power can be turned back on until the SPD is replaced in the event of SPD tripResi9 faq1

When does the Resi9 SPD need to be replaced?

Hide Show
The Resi9 surge protection device (SPD) comes with an end of life indication flag on the front face.
When the flag is white, the product will continue to help protect the installation against surges.
Resi9 NZ faq2However when the flag turns red, the SPD cartridge needs to be replaced to continue to protect the installation against surge currents.

How do I replace the Resi9 SPD cartridge?

Hide Show
Instructions to replace the Resi9 SPD cartridge (R9L40102) are clearly illustrated in the attached Resi9 SPD instruction sheet.

Resi9 NZ faq2

Does the Resi9 SPD cartridge need to replaced only by a licensed electrician?

Hide Show
Yes, it is recommended to go through licensed electrician for the replacement of Resi9 SPD.
Resi9 faq2