Browse all
Browse all

Acti9 Arc Fault Detection Circuit Breaker iDPN N VigiARC C 25A 6000A 30mA Type A 25A

Home ProductsCircuit ProtectionActi9Arc Fault Detection Circuit Breaker

Acti9 Arc Fault Detection Circuit Breaker iDPN N VigiARC C 25A 6000A 30mA Type A 25A

Item Number: A9T26625

Datasheet

Product Dimensions

Width icon

Width36 mm

Height icon

Height91 mm

Depth icon

Depth75 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range Acti9
Product or component type arc fault detection RCBO
Warranty 24 months

Physical

Standards
  • EN/IEC 62606
  • AS/NZS 61009.1
[in] rated current 25 A
[ue] rated operational voltage
  • 230/240 V AC 50 Hz conforming to AS/NZS 61009.1
  • 230/240 V AC 50 Hz conforming to IEC 62606
Control type toggle
Local signalling ON, OFF, fault trip
Mounting mode clip-on
Mounting support DIN rail
Mechanical durability 20000 cycles
Electrical durability 10000 cycles 240 V AC 50 Hz conforming to AS/NZS 61009.1
Cable entry top and bottom
Connections - terminals
  • tunnel type terminal for 2 cable(s) 2.5-2.5 mm² rigid
  • tunnel type terminal for 1 cable(s) 16-16 mm² rigid
  • tunnel type terminal for 2 cable(s) 2.5-2.5 mm² flexible
  • tunnel type terminal for 1 cable(s) 10-10 mm² flexible
Wire stripping length 14 mm
Height 91 mm
Width 36 mm
Depth 75 mm
Net weight 205 g
Ip degree of protection IP20 conforming to IEC 60529
Relative humidity 95 % at 55 °C
Ambient air temperature for operation -25...60 °C
Ambient air temperature for storage -40...80 °C
Mercury free Yes
Rohs exemption information Yes
Environmental disclosure ENVPEP2205013EN
Eu rohs directive Compliant By Exemption

Others

Life cycle assessment data Yes
Legacy weee scope In
Package 1 bare product quantity 1
Average percentage of recycled plastic content 0 %
Outside of Europe
Warranty duration(in months) bmecat 24
Weee label N/A
Product name Acti9 iDPN N VigiARC
Device short name iDPN N VigiARC
Product specific application arc fault detection
Poles description 1P + N
Number of protected poles 1
Curve code C
Breaking capacity code N
Breaking capacity 6000 A at 240 V AC 50 Hz conforming to AS/NZS 61009.1
Rated breaking and making capacity Idm 500 A at 240 V AC 50 Hz conforming to AS/NZS 61009.1
Neutral position left
Network type AC
Earth-leakage protection time delay instantaneous
Earth-leakage protection class class A
Suitability for isolation yes
Residual current tripping technology voltage dependent
Trip unit technology thermal-magnetic
Earth-leakage protection integrated
Network frequency 50 Hz
Device location in system outgoer
Magnetic tripping limit 5...10 x In
Limitation class 3 conforming to AS/NZS 61009.1
[ui] rated insulation voltage
  • 250 V AC 50 Hz between phase and neutral
  • 400 V AC 50 Hz between phases
Threshold tripping voltage 275 V for +/- 5 V
[uimp] rated impulse withstand voltage 4 kV conforming to AS/NZS 61009.1
Contact position indicator yes
Overvoltage category III
Locking options description padlocking device
Tightening torque 2 N.m
Comb busbar and distribution block compatibility YES
9 mm pitches 4
Power losses per pole 6.5 W
Heat dissipation 6.50...6.50 W at 240 V - 25 A
Pollution degree
  • 2 conforming to AS/NZS 61009.1
  • 2 conforming to IEC 62606
Tropicalisation severity B conforming to IEC 60068-2-30 for 28 d
Operating altitude 2000 m
Quality labels RCM
Unit type of package 1 PCE
Number of units in package 1 1
Package 1 height 7.5 cm
Package 1 width 3.6 cm
Package 1 length 9.1 cm
Package 1 weight 240.0 g
Green premium status for reporting Green Premium product
Sustainable packaging No
Pvc free No
Silicone-free  No
Energy efficiency optimized False
F-gas free N/A
Updatability N/A
Take-back No
Product contributes to saved and avoided emissions No
Removable battery N/A
Average percentage of recycled metal content 0 %
Packaging made with recycled cardboard No
Packaging without single use plastic No
Scip number b078722f-7853-4e1e-a05b-29638f57b0ab
Pvc free No
Silicone-free No
End of life manual availability ENVEOLI2205013EN
Take-back No
Warranty (in months) 24

Documents & downloads

Filter items
  • All

  • CAD Files and Packs

  • How to video

  • End of Life Manual

  • Environmental Disclosure

  • Installation Instruction

  • Certificates (MSDS)

  • Declaration of Conformity (Sustainability)

Important: Some software files may need a mySchneider or Club login to download.