Frequently asked questions
How can ATS01N2...LU, QN, RT be started without external control wires?
FA166828
20 July 2022
Issue:Start ATS01N2...LU, QN, RT without control wires.
Product Line:
Altistart 01 Soft Starters with "LU", "QN", or "RT" at the end of the part number
Environment:
All
Cause:
Need to start the Soft Starter with power up
Resolution:
Add a jumper between terminals LI+ and LI2. This provides a continuous RUN command. When power is supplied to the ATS01, it will immediately begin to start the motor. Removing power will result in a freewheel stop.