R2 can not be changed in the I/O Menu on the ATV61 and ATV71 drives?
FA177873
28 September 2021
Issue:Issues changing R2 in the I/O Menu on the ATV61 and ATV71 drives.
Product Line:
ATV61 ATV71 Altivar
Environment:
All
Cause:
Programming change for R2 relay.
Resolution:
Check to verify no run command being commanded or the drive is in RDY state.
Check menu 1.7 application function to see if output contactor command (OCC) or BLC is not assigned to R2.