Can I assign a different logic input other than LI1/DI1 to run forward on an Altivar drive?

FA247077

25 November 2022

Issue:
Set logic inputs other than LI1/DI1 for run forward command on an Altivar drive.
 
Product Line:
Altivar drives 
 
Environment:
All 

Cause :
LI1 logic input inoperative

Resolution:
In 2 wire control, LI1/DI1 is run forward. In 3 wire control, LI1/DI1 is stop and LI2/DI2 is run forward.
In either configuration, LI/DI1 must be active for the drive to run and no other inputs can be assigned as run forward. 


 

 

;