Frequently asked questions
What is the ambient temperature operating range of the ATV12 series drives?
FA274744
15 July 2022
Issue:ATV12 ambient temperature operating range
Product Line:
ATV12 series drives.
Environment:
All models, All serial numbers.
Cause:
N/A
Resolution:
Ambient Air Temperature**
ATV12H018F1, ATV12H037F1
ATV12H018M2...H075M2
ATV12H018M3...H075M3
ATV12P models
Operation -10C to +40C without derating. Up to +60C with derating. Remove the blanking cover and de-rate at 2% per degree above 40C.
ATV12H075F1
ATV12HU15M2, HU22M2
ATV12HU15M3...HU40M3
Operation -10C to +50C without derating. Up to +60C with derating. Remove the blanking cover and de-rate at 2% per degree above 50C.
Storage temperature for all units is -25C to +70C
** UL ratings are up to 40C only. Higher temperature ratings listed above are for non-UL listed applications only.