This table lists the UL endurance test requirements for different frame sizes:
 
Frame Size (A)Full Load OperationsNo Load Operations
0-100                              6,000                                    4,000
101-225                              4,000                                    4,000
226-600                              1,000                                    5,000
601-800                                 500                                    3,000
801-2500                                 500                                    2,000