Acti9 Arc fault detection circuit breaker iDPN N Arc, 1P+N 6A C 6000A

Home ProductsCircuit ProtectionActi 9Arc fault detection circuit breaker

Acti9 Arc fault detection circuit breaker iDPN N Arc, 1P+N 6A C 6000A

Item Number: A9FDB606

Datasheet

Product Dimensions

Width icon

Width36 mm

Height icon

Height81 mm

Depth icon

Depth72 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

Acti9

Range

Acti9

Product or component type

arc fault detection circuit breaker

Sustainable offer status

Green Premium product

Physical

Standards

EN/IEC 62606|IEC 60898-1

[in] rated current

6 A at 30 °C

[ue] rated operational voltage

230 V AC 50 Hz conforming to IEC 62606|230 V AC 50 Hz conforming to EN/IEC 60898-1

Control type

toggle

Local signalling

ON, OFF, fault trip

Mounting mode

clip-on

Mounting support

DIN rail

Mechanical durability

20000 cycles

Electrical durability

20000 cycles 230 V AC 50 Hz

Cable entry

top

Connections - terminals

tunnel type terminal for 1 cable(s) 10-10 mm² flexible|tunnel type terminal for 2 cable(s) 2.5-2.5 mm² flexible|tunnel type terminal for 1 cable(s) 16-16 mm² rigid|tunnel type terminal for 2 cable(s) 2.5-2.5 mm² rigid

Wire stripping length

14 mm

Height

81 mm

Width

36 mm

Depth

72 mm

Net weight

190 g

Ip degree of protection

IP20

Ambient air temperature for operation

-25...60 °C

Ambient air temperature for storage

-40...85 °C

Product certifications

RCM

Eu rohs directive

Compliant with Exemptions

Mercury free

Yes

Rohs exemption information

Yes

China rohs regulation

Product out of China RoHS scope. Substance declaration for your information

Environmental disclosure

ENVPEP1312033EN

Circularity profile

ENVEOLI1312033EN

Others

Package 1 bare product quantity

1

Circuit breaker application

distribution

Product name

Acti9 iDPN N Arc

Product specific application

fire prevention by arc detection

Device short name

iDPN N Arc

Poles description

1P + N

Curve code

C

Breaking capacity

6000 A Icn at 230 V AC 50 Hz conforming to EN/IEC 60898-1

Network type

AC

Neutral position

left

Trip unit technology

thermal-magnetic

Number of protected poles

1

Network frequency

50 Hz

Device location in system

outgoer

Magnetic tripping limit

5...10 x In

Limitation class

3 conforming to IEC 60898-1

Threshold tripping voltage

400 V 200 ms

[uimp] rated impulse withstand voltage

4 kV conforming to IEC 60898-1

[ui] rated insulation voltage

400 V AC

Contact position indicator

yes

Overvoltage category

III

Tightening torque

2 N.m

Comb busbar and distribution block compatibility

ProDis|Librio

Connection pitch

9 mm between phase and neutral

9 mm pitches

4

Heat dissipation

2.7...2.7 W at 230 V - 6 A

Pollution degree

2

Tropicalisation

severity B conforming to IEC 60068-2-30 for 28 d

Operating altitude

2000 m

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

4.0 cm

Package 1 width

8.5 cm

Package 1 length

10.0 cm

Package 1 weight

220.0 g

Unit type of package 2

S02

Number of units in package 2

8

Package 2 height

15.0 cm

Package 2 width

30.0 cm

Package 2 length

40.0 cm

Package 2 weight

2.004 kg

Sustainable packaging

Yes

Weee

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Show all specifications