bracket mtg 1g std plaster

BRACKET MTG 1G STD PLASTER

Catalogue Number: 155P
bracket mtg 1g std plaster
Colour:
Colour: Per UOM Std.
  • 1 PCE 1

Specifications

hide show
Product brand
Clipsal
Product or component type
bracket
Accessory / separate part category
mounting accessory
Shape
square
Fixing center
84 mm
Depth
3 mm
Length
152 mm
Width
152 mm
Material
metal
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
Toxic heavy metal free
Yes
Mercury free
Yes
RoHS exemption information
Yes
China RoHS Regulation
 Pro-active China RoHS declaration (out of China RoHS legal scope)
Circularity Profile
N/A

Frequently Asked Questions

hide show

What is part number for Optiline 70 skirting duct 155x 55?

The part number for Optiline 70 skirting duct 155x 55 is a - ISM11450

For more information on this part please refer to https://www.clipsal.com/Trade/Products/ProductDetail?catno=ISM11450


User-added image

Read a LXM32 drive ramp (ACC, DEC) using SoMachine

Issue:
How to read a LXM32 drive ramp (ACC, DEC) using SoMachine?

Product Line:
Lexium 32

Resolution:
To read the drive ramp values (ACC, DEC), you can use the function block "MC_ReadParameter".
This function block requires the modbus address of the parameter in the input "Address".
ParameterNumber must be set to 1000 (Default value).
1556 = RAMP_v_acc
1558 = RAMP_v_dec

Using GetAttributeSingle would also work. In this case, the CIP address should be used (can be found in the LXM32M manual).
CIP 106.1.10 = RAMP_v_acc
CIP 106.1.11 = 1558 = RAMP_v_dec

What is the recommended line reactor part number for a 15HP 460VAC drive?

Issue:
What is the recommended line reactor part number for a 15HP 460VAC drive?

Product Line:
All

Environment:
All

Cause:
Input or output line/load reactor part numbers.

Resolution:
RL02503 is open style.
RL02513 is enclosed NEMA type 1.
Both are 5% reactors rated for 15HP 480V 3 phase.
This reactor will fit the ATV31HD11N4, ATV61HD11N4 and ATV71HD11N4 or any 15HP 460VAC drive.

What is the plaster bracket to suit the P2025?

The part name is 155P2

What is part number for bracket to suit BSL31VA?

The part number for bracket to suit is 155P.

Will 25/2V double outlet, large size, vertical fit on 155P2 plaster bracket?

Yes, 25/2V will fit on 155P2. 25/2V is  Large Size Format 115 x 115mm, Double Power Outlet rated to 250V 10A.
For further information please visit:
https://www.clipsal.com/Trade/Products/ProductDetail?catno=25/2V
User-added image

155P2 is a large plaster mounting bracket with 84mm mounting centre. For further information please visit:
https://www.clipsal.com/Trade/Products/ProductDetail?catno=155P2
User-added image
 

When is a neutral CT required?

Issue:
When is a neutral CT required?

Product Line:

Environment:

Cause:


Resolution:
A neutral CT is only required when there are loads that produce neutral current.
A neutral CT is required when an electronic-trip circuit breaker has a ground-fault option (alarm or trip) and is used on a 4 wire system. Neutral current must be factored in with phase current for accurate sensing.
A neutral CT is also required for the GFM modules when used on a 4-wire system.


CTA-ID : 1559

What would be the Wall plate (plaster) to suit Prestige large switches?

The wall plate would be the 155P2.

Please go to the website via the following link www.clipsal.com/Trade/Products/ProductDetail  and check under the Documentation Tab for more information.

What is the largest trunking we do in NZ

 The larges is Actassi 155 x 55 part code ISM11400


What is the part number for a PDL DOL Starter 240V 5.5Kw

PDL56DOL12LOBGY - less overload
available on page 155 Pocket book PDL 2014

What does RDY status on an Altivar drive mean?

Issue:
What does RDY status on an Altivar drive mean?
 
Product Line:
All Altivar drives
 
Environment:
All models currently in production, all serial numbers.
 
Cause:
Customer is unsure what this code indicates
 
Resolution:
RDY is an indication that the drive is ready to run and has not detected any faults, but does not currently have a command to run.  This is the normal status of the drive when it is powered, but does not have a run command present, or any other logic inputs triggered to disable the drive, such as a freewheel stop input or external fault input.

Installation Issues with Symmetra LX & 100A Supply

"

Symmetra LX is a redundant on-line double conversion UPS. Each Symmetra Power Module is rated at 4 KVA so when the Symmetra LX is fully populated with 5 power modules, it can draw up to16 KVA from the utility as one power module is redundant. This unit can be used either as a single phase or as a 3 phase unit, without any adjustments or changes being made to system to achieve this.

The Symmetra LX will operate at a voltage of 155 V to 276V , therefore it should draw a current of about 100A at 155V on a full load of 16KVA. Most European regulations require a 35 sq. mm cable for a 100A load but the Symmetra LX connectors will only take a maximum of 25 sq. mm.

However if we look at the power supply in most European countries, the voltage range is 230V - 240V and a voltage of under 200V would be very unusual. Taking a voltage of 240V and running the unit on full load the current would be just over the 65A, with 230V it would still be under 70A and we can drop the down to 200V before reaching 80A. The Symmetra LX should be protected by a slow blow Fuse / MCB which would need a sustained overload of over 1.2 times the rated current for about 2 hours to trip the Fuse / MCB, so even if the voltage drops below 200V the extra current shouldn't cause any problem.

In an area where a reasonably stable voltage exists there is no problem in using 25 sq. mm with an 80A fuse / MCB. Even with substantial voltage drops there is no danger of cables overheating or fuses blowing. In cases where the cable runs are very long and the regulations specify 35 sq. mm cable, the 35 sq. mm cable can be brought to the isolator adjacent to the unit and a 25 sq. mm cable can be used between isolator switch and UPS.

"

GetIDN_S and GetIDN_P 2 bytes in TSXCSYxx and MMS Sercos Modules

Goals and Symptoms

The purpose of this resolution is to inform the user on the behavior when using the command GetIDN_S (opcode 1556) or Get IDN_P ( opcode 1557 ) from a Quantum (or) a Premium SERCOS Controller.

Facts and Changes

When a 2 bytes IDN is gets the PLC haven't any possibility to know if the value is signed or not. So, the PLC register accommodate values from -32767 to + 32767 in signed format
Due to the above reason, values for IDN_S ( or _P ) 2 bytes set higher than 32767 when read, will be returned as follows:

(i) 32768 -> -32768
(ii) 32769-> -32767
(iii) 35000 -> -30536 in signed format. Unsigned format will result in a huge number.

Causes and Fixes

When GetIDN_S ( or _P ) returns a negative value, it may be converted to its positive equivalent by adding 65536.
For example, -30536 + 65536 = 35000 and so on. There is no implication on using the SetIDN_S ( or _P) command for the same IDN which is Unsigned decimal format.


Legacy KB System (APS) Data: RESL182198 V1.0, Originally authored by PhBr on 02/16/2007, Last Edited by PhBr on 02/16/2007
Related ranges: Modicon Premium

How to implement MFB (Motion Function Block) functionality for Lexium 05, Lexium 32, Lexium 15 and IclA drives in Unity Pro for M340?

Goals and Symptoms

How to implement MFB (Motion Function Block) functionality in a Modicon M340 for Lexium 05, Lexium 32, Lexium 15 and IclA drives in Unity Pro?

Facts and Changes

Reference of software used:
- Unity Pro 4.1 and Unity Pro 5.0.

- The standard version of the hardware catalog manager (ver 1.0) is included in both UnityPro versions 4.1 and 5.0

Causes and Fixes

The following is a step by step procedure on how to implement the MFB (Motion Function Block) functionality in a Modicon M340 for Lexium 05, Lexium 32, Lexium 15 and IclA drives in Unity Pro.

A . How to Configure the CANopen Slave?

1, In Unity Pro Project Browser, fully expand the Configuration directory and then double-click on CANopen. The CANopen window appears:



2. Select Edit / New device. The New Device window appears.


3. Under Motion&Drives select:

a. LXM05_MFB for LXM05A drive
b. LXM32_MFB for Lexium32A and Lexium32M drives. See "B. How to Upgrade the Hardware Catalog" if the LXM32_MFB is not listed.
c. Lexium15LP_V1_45 for a Lexium 15LP drive or Lexium15MH_V6_64 for a Lexium 15MP drive.
d. IclA_IFA, IclE_IFA or IclA_IFS for the corresponding IclA drives.

4. Select Edit / Open Module. If MFB has not already been selected, choose it in the Function area.

5. You will now be asked to validate your modifications when closing the CANopen window. This completes the implementation of the MFB functionality for the selected drive(s). For Lexium 32 series drives, please follow the procedure listed below to first upgrade the hardware catalog.

B. How to Upgrade the Hardware Catalog (applies for Lexium 32 drives)
(Note: All the drives mentioned above are part of the Hardware Catalog Manager version 1.0 except LXM32_MFB)

1. Open the Hardware Catalog: Start /Program / Schneider Electric / SoCollaborative / UnityPro / Hardware Catalog Manager. The Hardware Catalog Manager window appears:


2. To upgrade the catalog go to File / Import User Devices and then import the LXM32_MFB.cpxfile. The file is attached to this resolution.


C. Axis Creation and Configuration
1. Right-click on the Motiondirectory and then click on the New axis.
2. Clicking on the New axiscommand will open a dialog box with three tabs.
3. In the General tab, enter a name, selecta servodrive from the list and a compatible CANopen address
4 In the Axis Parameterstab, selectthe reference of the servodrive and the minimum version of the servodrives firmware
5. In the Variables Name tab, enter:a name for the Axis_Ref type variable linked to the servodrive and a name for the Can_Handler type variable linked to the servodrive
6. Click on OK to confirm the selections.

D. Availability of Blocks on the Various Servodrives

Not all blocks are available on all hardware platforms. The blocks available on your Modicon M340 platform with CANopen fieldbus can be found in the following tables:

.

For further details please refer to the MFB for Modicon M340 using Unity Pro - Start-up Guide attached to this resolution

This completes the procedure on implementing the MFB functionality in UnityPro..

Attachments

(Removed File URL: 204163_06C2/LXM32_MFB.cpx)(Removed Image URL: /PubResEXPORT.nsf/2b87ee90be777fc085257c28006ee4ef/833f1d1337661839c12577fa0016482f/fl_block_5/0.158?OpenElement&FieldElemFormat=gif) (Removed File URL: 204163_06C2/MFB_for_Modicon_M340_using_Unity_Pro_-_Start-up_Guide.pdf)(Removed Image URL: /PubResEXPORT.nsf/2b87ee90be777fc085257c28006ee4ef/833f1d1337661839c12577fa0016482f/fl_block_5/0.834?OpenElement&FieldElemFormat=gif)


Legacy KB System (APS) Data: RESL204163 V1.0, Originally authored by TVe on 12/15/2010, Last Edited by TVe on 12/15/2010
Related ranges: Modicon M340, Lexium 32

Does third-party equipment exist to test the AFCI to determine that it is functioning properly?

Product Line:
Circuit Breakers
QO and Homeline
AFI and AFCI

Environment:
Electrical Distribution Equipment

Resolution:
No. So-called AFCI ``testers`` are on the market, but they are not UL listed for testing the function of an AFI circuit breaker. UL 1436 refers to them as ``indicators`` rather than testers, and Square D does not endorse them or recommend their use. They are subject to error in the form of giving a false negative result.

The UL approved method of testing an AFCI circuit breaker is to press the push-to-test button when installed in an energized load center or panel. This test injects a signal into the AFCI sensor that looks like an arc to the AFCI. A properly functioning AFCI will trip when the test button is pushed.

Paragraph 31.8.1 of the UL 1436 standard requires the AFCI Indicator markings or instructions to effectively state that the test button on the AFCI circuit breaker demonstrates proper operation.
 

MES120, MES120G, MES120H Input/Output Modules Installation Sheet, Instruction Bulletin

Issue
Documentation request for the MES120, MES120G, MES120H Input/Output Modules Installation Sheet, Instruction Bulletin

Product Line
Sepam Series 80 Relay

Environment
Extending relay I/O

Resolution

MES120, MES120G, MES120H Input/Output Modules Installation Sheet, Instruction Bulletin (ANSI), 63230-216-242A1, May 2007
You can extend the five output relays included on the Sepam Series 80 base unit by adding one, two, or three MES120 modules with 14 DC logic inputs and six output relays, one control relay output, and five annunciation relay outputs.
Three modules are available for the different input supply voltage ranges and offer different switching thresholds:
MES120, 14 inputs 24 V DC to 48 V DC with a typical switching threshold of 14 V DC
MES120G, 14 inputs 220 V DC to 250 V DC with a typical switching threshold of 155 V DC
MES120H, 14 inputs 110 V DC to 125 V DC with a typical switching threshold of 82 V DC


Legacy KB System (APS) Data: RESL191286 V1.0
Related ranges: Sepam series 80, Sepam accessories

Are the windings double insulated from each other in the ABL6TS250U transformer?

The protection class of a transformer always related to the primary side.
If a PE is used, the device is automatically class1!
 
All our transformers are conforming Protection class 1, because they have an internal shield that must be connected to EARTH and so this leads to Class1.
We don't have any transformers in the offer that are conforming Protection class 2 (according to VDE 0106 1).
 
Regarding “double insulation” relates to the max. voltage that the transformer can withstand, the so called “Dielectric strength - Primary/secondary”
Here I can say, that Class1 requires 2kV and Class2 requires 4kV (which conforms to “double insulation”).
 
Our transformer ABL6TS250U meets the 4kV! (so this can be considered as "double insulation" even though the device itself is "Class1")
 
And last the Class F - is the electrical insulation class - meaning that the used insulation material can withstand a temperature up to 155 degrees Celsius.

Is there a C clip for 13mm gyprock as the 154 doesn't fit ?

No, The 154 is designed to suit  up to 12mm and then the 154/1 suits from 19-25mm . If These are not suitable then 155 series may be used

What is the difference between a Transformer's "temperature rise" and its "insulation class"?

Issue:
Explanation of the difference between temperature rise and insulation class specifications.

Product Line:
LV Transformers

Environment:
Applies to Low Voltage Transformers by SquareD/Schneider Electric

Cause:
Transformer Temperature Rise and Insulation Class are two different technical attributes

Resolution:

This question has come up because NEC 450-21(b) requires Transformers larger than 112.5 kVA to be installed in fire resistant construction unless the insulation class is 155 or higher.

The insulation system of a Transformer is rated in degrees Celsius at its maximum temperature rating (the Class number = the degree C of the insulation system; example, a Class 220 insulation system is rated for 220°C) Transformers have either a Class 220 (former designation "H") Class 180 (former designation "F",) Class 150 (former designation "B") or Class 105 (former designation "A") Some smaller manufacturers may also use a Class 200 (former designation "R").

The temperature rise of a Transformer is the average temperature rise that will occur in the coils during normal full load.

The insulation system <> standard temperature rise relationships are:
Class 220 <> 150 degree Celsius rise
Class 180 <> 115 degree Celsius rise
Class 150 <> 80 degree Celsius rise
Class 105 <> 50 degree Celsius rise

A Transformer with a Class 220 insulation system can be designed for a maximum temperature rise that is lower than the standard 150 degree Celsius. It can be designed for either 115 or 80 degree Celsius rise. As well, a Class 180 insulation system Transformer can be designed with 80 degree Celsius rise. Class 150 and 105 transformers are not typically designed for other than their standard temperature rise.

Since all Square D low voltage dry type Transformers larger than 112.5kVA are built with a 220 degree Celsius insulation system, exception #2 under NEC 450-21(b) applies.

Can I physically interconnect multiple NetBotz devices?

Issue: 

Can I physically interconnect multiple NetBotz devices? 

Product Line: 

NetBotz 

Environment: 

NBRK0200, NBRK0250, NBRK0450, NBRK0550, NBRK0570, NBWL0355, NBRK0455, or any of the older version 2 appliances. 

Cause: 

Customers often call asking if there is a way to physically interconnect NetBotz appliances without a network connection. 

Resolution: 

Other than a network connection, the only interconnection that should be done with NetBotz is to connect USB or A-link pods to a NetBotz appliance. You should never try to interconnect multiple NetBotz appliances through USB, A-link connections are only to be used for sensor pod 150 or 155 units or an AP9520TH. Similarly, the sensor ports should not be connected to anything other than the specific sensor or group of sensors for which it was designed. 

The A-link port is not a network connection and attempting to connect for instance a NetBotz NBRK0250 to another NBRK0250 using A-link ports has been seen to cause physical issues in some instances. It is advised that you only connect the sensor, network, or A-link cables to the proper ports and check the user manual should you be unsure.