cable c bus category 5

C-Bus Cable, 4 Pair, UTP Cable, Solid Conductor, 305 Metre

Catalogue Number: 5005C305B

Specifications

hide show
Package 1 Height
198 mm
Package 1 Length
370 mm
Package 1 width
378 mm
Range
C-Bus
Product brand
Clipsal
Product or component type
cable
Device application
communication
Colour
pink
Type of packing
carton
Type of cable
4 twisted-pairs cable
Bending radius
4 x overall diameter
Communication network category
5e
Transmission frequency
100 MHz
AWG gauge
AWG 24
Cable stiffness
solid class 1
Cable shielding type
U/UTP
Communication port protocol
  • 1000BASE-T conforming to IEEE 802.3u
  • PoE (Power over Ethernet) conforming to IEEE 802.3af
  • PoE+ (Power over Ethernet) conforming to IEEE 802.3at
    • Material
    • conductor: bare copper
    • insulation: polyolefin
    • jacket: LSZH (low smoke zero halogen)
    • rip cord: polyester multi yarn
      • Pulling force
        110 N
        Cable outer diameter
        5 mm +/- 0.2 mm
        Length
        305 m
        Net weight
        8.54 kg
        Ambient air temperature for installation
        0-60 °C
        Ambient air temperature for operation
        -20-60 °C
        Ambient air temperature for storage
        -20-60 °C
        Environmental characteristic
        LSZH (low smoke zero halogen)
        Directives
      • 2011/65/EU - RoHS directive
      • 2006/95/EC - low voltage directive
        • Product certifications
          CE
          Standards
        • ANSI/TIA-568-C.2:2009
        • ISO/IEC 11801:ed. 2.2
        • IEC 61156-5:ed. 2
        • IEC 60332-1-2
        • IEC 61034-1
        • IEC 61034-2
        • IEC 60754-2
          • Package 1 Weight
            9.52 kg
            Sustainable offer status
            Green Premium product
            REACh Regulation
            Free of Substances of Very High Concern above the threshold
            REACh free of SVHC
            Yes
            EU RoHS Directive
            Compliant
            Toxic heavy metal free
            Yes
            Mercury free
            Yes
            RoHS exemption information
            Yes
            China RoHS Regulation
            X
            Environmental Disclosure
            ENVPEP110210EN
            WEEE
            The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

            Documents & downloads

            hide show

            Frequently Asked Questions

            hide show

            What is the part number for a Cat5 pink cable

            Code is 5005C305B

            What is the outer diameter of the pink CBus cable 5005C305B ?

            The Nominal Diameter of the pink sheath is 5.2mm  ?
            Please follow the links provided to the Data sheet and clipsal website 
            https://www2.clipsal.com/cis/__data/page/428/5005C305B%20data%20sheet2.pdf
            https://www.clipsal.com/Trade/search-results?q=5005c305b
            User-added image

            Is the pink, C-Bus cable rated at 240 volts?

            Yes, The Pink outer sheath of the 5005C305B Cable is rated for 240 volts.
            However the internal conductors are not rated for 240 Volts

            Can C-Bus cable be used underground?

            C-Bus cable (5005C305B) does not go underground.
            If customer requires cable for underground use, they can use any CAT 5 or CAT 6 JELLY FILLED cable

            C-Bus - What is the Insulation rating of the C-Bus Cable?

            The C-Bus Cat5 cable working voltage has been tested, it's rated up to and inclucing 0.6/1 kV

            - See attached Certification for the C-Bus Cable.

            Is the Cbus cable stranded or solid core?

            Solid core Cbus cable is stocked, code 5005C305B
            Stranded Cbus cable is indent, code 5005C305BST 
            Show More