Can I confirm that we can achieve earth fault alarm without an external sensor in 3PH4W MTZ2 20H1 – Micrologic 5.0X?

FAQ000246655

14 December 2022

Issue:

Can we achieve earth fault alarm without an external sensor in 3PH4W

Product Line:

Circuit Breakers

Environment:

Masterpact MTZ, Micrologic X control unit

Resolution: 

As per MasterPact MTZ - MicroLogic X Control Unit User Guide, the ground -fault current is calculated or measured as below

MasterPact MTZ - MicroLogic X Control Unit User Guide Link:

https://www.productinfo.schneider-electric.com/micrologicxuserguide/doca0102-micrologic-x/English/DOCA0102EN-08.pdf


Ground Fault Current Calculating

The basic principle of ground fault current Ig is the vectorial sum= I1+I2+I3+In.
Please see below one example for better understanding:
1.      If customer is 3phase 4 wire system (with Neutral), there are two solutions of ground fault alarm/protection:
1)     Customer can select 3P breaker, but breaker should be configurated as 3P+ENCT, that means the external neutral CT sensor is necessary.
2)     Customer can select 4P breaker, no necessary for external neutral CT sensor.

2.      If customer is 3phase 3 wire system (without Neutral):
Customer should select 3P breaker and declares the ENCT to “NO”, no necessary for external neutral CT sensor.
Anyway, if there is neutral phase in customer system, neutral current should be measured in 4P or 3P with external sensor.
 
;